| Plan Review Notes For Permit 06011232 |
| Permit Number |
06011232 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-03-15 00:00:00 | | | | | | | DENIED | | | | | | 1) ENGINEER IS USING OUTDATED SEAL. NEW | | | SEAL IS TO BE USED AFTER JAN.1, 2006 PER | | | RULE 61G15-23.001(1), FAC | | | | | | 2) BY SIGNING AND SEALING THESE DRAWING | | | THE ENGINEER IS TAKING RESPONSABILITY | | | FOR THEM. THEIR IS NO STRUCTURAL | | | THEREFORE REMOVE NOTE #10 FROM DRAWING | | | | | | 3) DWELLING UNITS SHALL BE SEPERATED BY | | | A 1-HOUR FIRE RESISTIVE RATING PER R317 | | | FBC. PROVIDE DETAIL FOR CEILING AND | | | STAIRWELL WALLS | | | | | | 4) BATHROOM DOORS SHALL MEET | | | ACCESSABILITY REQUIREMENTS PER R322 FBC | | | | | | 5) SMOKE ALARMS ARE REQUIRED AT TOP AND | | | BOTTOM OF STAIRS SEE THIS AND OTHER RED | | | LINES ON ELECTRICAL DRAWING | | | | | | NOTE: FBC = FLORIDA BUILDING CODE 2004 | | | FBC* = WEST PALM BEACH | | | ADMINISTATIVE AMMENDMENTS TO FBC | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | | | | | | | | | | | | | | | | | | | | | | |
|