2006-03-15 00:00:00 
  
 DENIED
  
 1) ENGINEER IS USING OUTDATED SEAL. NEW
 SEAL IS TO BE USED AFTER JAN.1, 2006 PER
 RULE 61G15-23.001(1), FAC
  
 2) BY SIGNING AND SEALING THESE DRAWING
 THE ENGINEER IS TAKING RESPONSABILITY
 FOR THEM. THEIR IS NO STRUCTURAL
 THEREFORE REMOVE NOTE #10 FROM DRAWING
  
 3) DWELLING UNITS SHALL BE SEPERATED BY
 A 1-HOUR FIRE RESISTIVE RATING PER R317
 FBC. PROVIDE DETAIL FOR CEILING AND
 STAIRWELL WALLS
  
 4) BATHROOM DOORS SHALL MEET
 ACCESSABILITY REQUIREMENTS PER R322 FBC
  
 5) SMOKE ALARMS ARE REQUIRED AT TOP AND
 BOTTOM OF STAIRS SEE THIS AND OTHER RED
 LINES ON ELECTRICAL DRAWING
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004
 FBC* = WEST PALM BEACH
 ADMINISTATIVE AMMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  