| Notes |
| Date |
Text |
| 2006-03-22 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE GROUNDING ELECTRODE CONDUCTOR | | | MUST BE BONDED TO FOOTER STEEL PER | | | 250.52(A)(3). | | | | | | 2} THE SERVICE ENTRANCE CONDUCTORS ARE | | | TOO SMALL FOR A 200 AMP SERVICE. SEE | | | 310.16(B)(6). | | | | | | 3} PLEASE SUBMIT A PANEL SCHEDULE SO | | | THAT BRANCH CIRCUIT COMPLIANCE CAN BE | | | REVIEWED. | | | | | | 4} THE PLAN SHOWS AN ADDED A/C SYSTEM. | | | THIS NEEDS TO BE ADDED TO THE | | | CALCULATION, AND AT 100%, SEE 220.31(B). | | | | | | 5} THE BATH RECEPTACLES MUST BE GFI PER | | | 210.8(A)(1). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|