 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE GROUNDING ELECTRODE CONDUCTOR
 MUST BE BONDED TO FOOTER STEEL PER
 250.52(A)(3).
  
 2} THE SERVICE ENTRANCE CONDUCTORS ARE
 TOO SMALL FOR A 200 AMP SERVICE. SEE
 310.16(B)(6).
  
 3} PLEASE SUBMIT A PANEL SCHEDULE SO
 THAT BRANCH CIRCUIT COMPLIANCE CAN BE
 REVIEWED.
  
 4} THE PLAN SHOWS AN ADDED A/C SYSTEM.
 THIS NEEDS TO BE ADDED TO THE
 CALCULATION, AND AT 100%, SEE 220.31(B).
  
 5} THE BATH RECEPTACLES MUST BE GFI PER
 210.8(A)(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  