| 2006-03-21 00:00:00 | |
| | |
| | DENIED |
| | |
| | 1) GLASS BLOCK WILL REQUIRE IMPSCT |
| | PROTECTION PER 1609.1.4 FBC SUBMIT |
| | PRODUCT APPROVALS FOR SHUTTERS |
| | |
| | 2) NO PRODUCT APPROVALS WERE SUBMITTED |
| | FOR FRENCH DOORS OR HORIZONTAL SLIDER |
| | |
| | 3) ALL PRODUCT APPROVALS WERE SUBMITTED |
| | WITH ONLY THE STATE COVER SHEETS PLEASE |
| | SUMIT THE NOA'S, EVALUATION REPORTS |
| | AND/OR INSTALLATIONSHEETS THAT GO WITH |
| | THE COVER SHEET |
| | |
| | 4) TWO STATE COVER SHEETS FOR SHINGLES |
| | FROM TWO DIFFERENT MANUFACTURERS PLEASE |
| | CLARIFY |
| | |
| | 5) PRODUCT APPROVALS SHALL BE APPROVED |
| | BY DESIGNER OF RECORD PER 106.3.3 FBC* |
| | |
| | 6) PROVIDE ENGINEERED TRUSS DRAWINGS |
| | WITH SUBMITAL PER R802.10 FBC |
| | |
| | 7) PROVIDE ATTIC ACCESS LOCATION AND |
| | SIZE ON DRAWINGS THAT COMPLY WITH R807.1 |
| | ALSO SEE M/E 100 AS FLOURESCENT FIXTURE |
| | MAY CROSS ACCESS |
| | |
| | 8) PROVIDE 2 COPIES OF ENERGY CALCS AND |
| | MANUEL J |
| | |
| | 9) SHOW DETAIL OF NEW BEAM-EXISTING |
| | TRUSS CONNECTION WITH LUS26 |
| | |
| | 10) PROVIDE FIN. FL. ELEVATION, BEAM |
| | ELEVATION, ROOF PITCH AND ELAVATION, AND |
| | MEAN ROOF HEIGHT ON A/200 |
| | |
| | 11) RADON FEE SHALL BE COLLECTED FOR THE |
| | STATE ON SQUARE FOOTAGE BEING ADDED PER |
| | 10D-91 FAC |
| | |
| | 12) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT IS REQUIRED PRIOR TO A |
| | PERMIT BEING ISSUED |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | 561-805-6716 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |