Plan Review Notes
Plan Review Notes For Permit 06011202
Permit Number 06011202
Review Stop B
Sequence Number 1
Notes
Date Text
2006-03-21 00:00:00 
  
 DENIED
  
 1) GLASS BLOCK WILL REQUIRE IMPSCT
 PROTECTION PER 1609.1.4 FBC SUBMIT
 PRODUCT APPROVALS FOR SHUTTERS
  
 2) NO PRODUCT APPROVALS WERE SUBMITTED
 FOR FRENCH DOORS OR HORIZONTAL SLIDER
  
 3) ALL PRODUCT APPROVALS WERE SUBMITTED
 WITH ONLY THE STATE COVER SHEETS PLEASE
 SUMIT THE NOA'S, EVALUATION REPORTS
 AND/OR INSTALLATIONSHEETS THAT GO WITH
 THE COVER SHEET
  
 4) TWO STATE COVER SHEETS FOR SHINGLES
 FROM TWO DIFFERENT MANUFACTURERS PLEASE
 CLARIFY
  
 5) PRODUCT APPROVALS SHALL BE APPROVED
 BY DESIGNER OF RECORD PER 106.3.3 FBC*
  
 6) PROVIDE ENGINEERED TRUSS DRAWINGS
 WITH SUBMITAL PER R802.10 FBC
  
 7) PROVIDE ATTIC ACCESS LOCATION AND
 SIZE ON DRAWINGS THAT COMPLY WITH R807.1
 ALSO SEE M/E 100 AS FLOURESCENT FIXTURE
 MAY CROSS ACCESS
  
 8) PROVIDE 2 COPIES OF ENERGY CALCS AND
 MANUEL J
  
 9) SHOW DETAIL OF NEW BEAM-EXISTING
 TRUSS CONNECTION WITH LUS26
  
 10) PROVIDE FIN. FL. ELEVATION, BEAM
 ELEVATION, ROOF PITCH AND ELAVATION, AND
 MEAN ROOF HEIGHT ON A/200
  
 11) RADON FEE SHALL BE COLLECTED FOR THE
 STATE ON SQUARE FOOTAGE BEING ADDED PER
 10D-91 FAC
  
 12) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO A
 PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW