| 2007-01-30 11:59:21 | REVISION DENIED |
| | REFERENCE: FBC-2004 PLUMBING; CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC-2004, CHAPTER 1, ADMINISTRATION; |
| | FBC-2004 CHAPTER 11. |
| | |
| | THIS IS A TENANT BUILD OUT COMPLETE SET OF PLANS AND |
| | SEPERATE PERMIT REQUIRED. |
| | THE FOLLOWING CORECTIONS ARE REQUIRED FOR PLUMBING PLAN |
| | REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. THE TWO COPIES OF PRINTS NEED TO BE STAMPED AND THE |
| | TWO PAGE WORK SHEETS NEED TO BE COMPLETED AND ATTACHED |
| | TO PRINTS BY DPBR HOTEL AND RESTAURANT DIVISION ON THE |
| | RESUBMITTAL PER FBC-2004 CHAPTER 1 SECTION 102.2.1. |
| | |
| | 2. SHEETS P-1 AND P-2 INDICATE AN ABOVE GROUNDGREASE |
| | INTERCEPTOR IN THE BUILDING. PER CITY OF WEST PALM |
| | BEACH CODE SECTION 90.124 (7) (B) GREASE INTERCEPTORS |
| | (SEPERATORS, GREASE TRAPS) ARE TO BE INSTALLED OUTSIDE |
| | OF THE FOOD PREPERATION AREA WITH THE DISHWASHER |
| | DISCHARGING VIA A SEPERATE LINE. (F) EACH INTERCEPTOR |
| | SHALL BE CONSTRUCTED OF STEEL REINFORCED CONCRETE. |
| | CLEANOUTS SHALL BE STEEL MANHOLE COVERS. NO FIBERGLASS |
| | INTERCEPTORS SHALL BE INSTALLED. |
| | NOTE: FOR THIS APPROVAL OR A WAIVER PLEASE CONTACT THE |
| | FOLLOWING. |
| | ENVIRONMENTAL COMPLIANCE MANAGER |
| | LYNN MASSON (561) 822-2271 |
| | FAX (561) 822-2279 |
| | E-MAIL- [email protected] |
| | |
| | 3. SHEETS P-1 FLOOR PLAN DOES NOT REFECT THE SANITARY |
| | RISER DIAGRAM AND SHEET P-2 SANITARY RISER DIAGRAM DOES |
| | NOT REFECT THE FLOOR PLAN. PLEASE CORRELATE AND |
| | RESUBMIT. PER FBC-2004 CHAPTER 1 SECTION 106.1, |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE. |
| | |
| | 4. SHEET P-2 GREASE RISER DIAGRAM MISSING FLOOR DRAIN |
| | AND PER FBC-2004 PLUMBING, TABLE 403.1 A SERVICE SINK |
| | REQUIRED. |
| | NOTE: FLOOR DRAIN AND SERVICE SINK SHALL DRAIN INTO THE |
| | GREASE INTERCEPTOR. |
| | |
| | 5. SHEET P-1 BATH ROOMS: ALL TOILET ROOMS SHALL BE |
| | ACCESSIBLE: SUBMIT A FLOOR PLAN DETAIL AND AN ELEVATION |
| | DETAIL SHOWING COMPLIANCE WITH FBC-2004 CHAPTER 11 |
| | FLORIDA ACCESSIBILITY CODE FOR BUILDING CONSTRUCTION, |
| | SECTIONS 11-4.16, 11-4.19 AND 11-4.22 AND ALL |
| | SUBSECTIONS. |
| | |
| | 6. SHEET P-2 WATER ISOMETRIC: PER FBC-2004 PLUMBING |
| | SECTION 608 PROTECTION OF POTABLE WATER SUPPLY, PLEASE |
| | INDICATEA RPZV BACKFLOW PREVENTER ON THE |
| | RESUBMITTAL. |
| | |
| | 7. SHEET P-2 PLUMBING GENERAL NOTES: A} PLEASE CHANGE |
| | NOTE #1 TO READ, ALL WORK SHALL BE DONE IN ACCORDANCE |
| | WITH THE FBC-2004 AND WITH ALL APPLICABLE REGULATIONS. |
| | B}PLEASE ADD TO NOTE #16, WATER HAMMER ARRESSTORS PER |
| | FBC-2004 PLUMBING SECTION 604.9. |
| | |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN |
| | REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 8. SHEET P-2 GAS ISOMETRIC: PER FBC-2004 FUEL GAS |
| | SECTION 404.14.1 LIMITATIONS. PLASTIC PIPE SHALL BE |
| | INSTALLED OUTSIDE UNDERGROUND ONLY. PLASTIC PIPE SHALL |
| | NOT BE USED WITHIN OR UNDER ANY BUILDING OR SLAB OR BE |
| | OPERATED AT PRESSURES GREATER THAN 100 PSIG FOR NATURAL |
| | GAS OR 30 PSIG FOR LP GAS. |
| | |
| | 9. SHEET P-2 GAS ISOMETRIC: EMERGENCY HOOD SHUT DOWN |
| | SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | |
| | |
| | **********IMPORTANT INFORMATION |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |