| 2006-06-15 00:00:00 | PERMIT: 06011130 |
| | ADD: 2037 SPRUCE AVE |
| | CONT:PLAN REVIEW |
| | "WEST PALM BEACH HOUSING |
| | AUTHORITY" |
| | TEL: (561)655-8530 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 1) COMMENET# 6 FROM THE PREVIOUS REVIEW, |
| | WPB ADMIN CODE 106.3* PRODUCT APPROVALS. |
| | THOSE PRODUCT WHICH ARE REGULATED BY DCA |
| | RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 2)COMMENT# 12 FROM THE PREVIOUS REVIEW, |
| | REPORT IS A COPY NOT RAISED SEAL. FL BLD |
| | CODE 1804.2.2 QUESTIONABLE SOILS, WHERE |
| | THE BEARING CAPACITY IS |
| | NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| | WHERE THE BEARING CAPACITY OF THE SOIL |
| | IS NOT DEFINITLY KNOWN OR IS IN QUESTION |
| | THE BUILDING OFFICIAL MAY REQUIRE EXPLOR |
| | ATIONS, TEST OR OTHER ADEQUATE PROOF AS |
| | TO THE PERMISSIBLE SAFE BEARING |
| | CAPACITY. REQUIRED TEST AND RECOMMENDA- |
| | TIONS SUBMITTED TO VERIFY BEARING CAPA- |
| | CITY SHALL BE CERTIFIED BY A GEOTECH- |
| | NICALREPORT FROM A DESIGN PROFESSIONAL |
| | PROPERLY LICENSED IN THE STATE OF |
| | FLORIDA. |
| | |
| | 3) COMMENT# 16 FROM THE PREVIOUS REVIEW, |
| | FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) TRUSS ANCHORS |
| | B) ROOF ASSEMBLIES |
| | C) STORM SHUTTERS |
| | ROOF ASSEMBLIES, HIGHLIGHT WHICH |
| | SUBSYSTEM THAT WILL BE USED, ALSO SEE IF |
| | REPORT WILL REQUIRE ENHANCED FASTENING |
| | LIMITATION# 7 OR 9. |
| | |
| | INDICATE WHERE STORM SHUTTERS WILL BE |
| | STORED? |
| | FL BLD CODE 2001 SECTION 103.6, |
| | 1606.1.4, 1707.4 & 3401.7.2.4. |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING |
| | OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| | BAR REINFORCING REQUIREMENTS, WALL PRES- |
| | SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION |
| | TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. |
| | PROVIDE STORM PANEL INFORMATION WITH |
| | INSTALLATION SCHEDULE AND KEY PLAN WITH |
| | SPECIFIC ANCHORS AND MOUNTING TO BE USED |
| | FOR ALL NON-IMPACT GLAZING. |
| | FBC 1606.1.4. |
| | |
| | 4) COMMENT# 18 FROM THE LAST REVIEW, |
| | A200 & A500 DOOR WAY ND01 PLANS INDICATE |
| | THE USE OF (2) 2'-8" DOORS. SEE |
| | 11-4.13.5 A MINIMUM OF 32" CLEAR WIDTH |
| | REQUIRED. |
| | |
| | 5) A401 & S204 COMMENT# 30 FROM THE |
| | PREVIOUS REVIEW, PLANS INDICATE A |
| | CONCRETE DECK, PROVIDE STEEL SIZE AND |
| | LAYOUT FOR THE 2ND FLOOR CONCRETE DECK. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |
| | |