| 2006-04-01 00:00:00 | PAUL SCHMITZ |
| | [email protected] |
| | FBC 2004 PLUMBING CODE PLAN REVIEW |
| | FBC2004 FUEL GAS CODEPLAN REVIEW |
| | FBC 2004 CH 11, FL ACESSIBILITY CODE |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPT.1, ADMINISTRATION, 2004 EDITION |
| | DENIED |
| | |
| | 1)NOTE: PLEASE BE SURE PLANS REFERENCE |
| | CURRENT CODES IN EFFECT FOR THIS SCOPE |
| | OF WORK. |
| | PLEASE SEE COVER SHEET(S) WHICH |
| | REFERENCE THE 2001 FBC? |
| | PLEASE SEE OTHER SHEET REFLECT THE 2004. |
| | PLEASE BE SURE PLANS ALSO REFERENCE THE |
| | 2002 NFPA-72, 2003 NFPA-101, 2002 |
| | NFPA-70 |
| | |
| | 2)NOTE: PLEASE SEE PLANS SUBMITTED ARE |
| | NOT SIGNED, DATED OR SEALED BY ARCHITECT |
| | OR ENGINEER;S OF RECORD. THIS IS NOT |
| | REQUIRED WHEN SUBMITTING FOR"PLAN |
| | REVIEW" , HOWEVER IS REQUIRED WHEN |
| | SUBMITTING FOR PERMIT. |
| | FS 481.221,471.025 |
| | |
| | 3)NOTE: PLEASE SEE MISSING FIRM LICENSE |
| | NUMBER FOR ARCHITECTURAL FIRM. FLORIDA |
| | ADMINISTRATIVE CODE, 61G1-16.004, FS |
| | 481.219 |
| | PLEASE KNOW, THIS IS REQUIRED ON ALL |
| | SHEETS AND FOR ALL TRADES WHICH CONTAIN |
| | THE TITLE BLOCK FOR ARCHITECTURAL FIRM. |
| | THIS COMMENT STANDS FOR ALL REVIEWS |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER |
| | REVIEWER(S). |
| | |
| | 4) PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | 5) SHT P-201 |
| | SEC 607.3 THERMAL EXPANSION CONTROL. |
| | A MEANS OF CONTROLLING INCREASED |
| | PRESSURE CAUSED BY THERMAL EXPANSION |
| | SHALL BE PROVIDED WHERE REQUIRED IN |
| | ACCORDANCE WITH SECTIONS 607.3.1 AND |
| | 607.3.2. |
| | |
| | 6) PROTECTION OF POTABLE WATER SUPPLY |
| | 608.1 GENERAL. |
| | A POTABLE WATER SUPPLY SYSTEM SHALL BE |
| | DESIGNED, INSTALLED AND MAINTAINED IN |
| | SUCH A MANNER SO AS TO PREVENT |
| | CONTAMINATION FROM NONPOTABLE LIQUIDS, |
| | SOLIDS OR GASES BEING INTRODUCED INTO |
| | THE POTABLE WATER SUPPLY THROUGH |
| | CROSS-CONNECTIONS OR ANY OTHER PIPING |
| | CONNECTIONS TO THE SYSTEM. BACKFLOW |
| | PREVENTER APPLICATIONS SHALL CONFORM TO |
| | TABLE 608.1, EXCEPT AS SPECIFICALLY |
| | STATED IN SECTIONS 608.2 THROUGH |
| | 608.16.9. |
| | (RPZV REQUIRED ON WATER SERVICE) |
| | |
| | END OF COMMENTS, QUESTIONS 561-805-6692 |
| | |
| | |
| | |
| | |