| Date |
Text |
| 2006-03-02 00:00:00 | ********** UNSAT ********** |
| | |
| | ** PLEASE KNOW, PLANS WERE SUBMITTED FOR |
| | "PLAN REVIEW" ONLY NAD HAVE NOT BEEN |
| | SUBMITTED FOR PERMIT. |
| | |
| | 1)NOTE: PLEASE BE SURE PLANS REFERENCE |
| | CURRENT CODES IN EFFECT FOR THIS SCOPE |
| | OF WORK. |
| | PLEASE SEE COVER SHEET(S) WHICH |
| | REFERENCE THE 2001 FBC? |
| | PLEASE SEE OTHER SHEET REFLECT THE 2004. |
| | PLEASE BE SURE PLANS ALSO REFERENCE THE |
| | 2002 NFPA-72, 2003 NFPA-101, 2002 |
| | NFPA-70 |
| | |
| | 2)NOTE: PLEASE SEE PLANS SUBMITTED ARE |
| | NOT SIGNED, DATED OR SEALED BY ARCHITECT |
| | OR ENGINEER;S OF RECORD. THIS IS NOT |
| | REQUIRED WHEN SUBMITTING FOR"PLAN |
| | REVIEW" , HOWEVER IS REQUIRED WHEN |
| | SUBMITTING FOR PERMIT. |
| | FS 481.221,471.025 |
| | |
| | 3)NOTE: PLEASE SEE MISSING FIRM LICENSE |
| | NUMBER FOR ARCHITECTURAL FIRM. FLORIDA |
| | ADMINISTRATIVE CODE, 61G1-16.004, FS |
| | 481.219 |
| | PLEASE KNOW, THIS IS REQUIRED ON ALL |
| | SHEETS AND FOR ALL TRADES WHICH CONTAIN |
| | THE TITLE BLOCK FOR ARCHITECTURAL FIRM. |
| | THIS COMMENT STANDS FOR ALL REVIEWS |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER |
| | REVIEWER(S). |
| | |
| | 4)NOTE: PLEASE KNOW, CUNDUIT IN OPEN |
| | TENANT SPCE SHALL BE PROTECTED, BY BEING |
| | SCHEDULE 80 OF PVC OR RIGID METAL ETC. |
| | 352,354,358 |
| | |
| | 5)NOTE: PLEASE SEE THAT THE ADDRESS OF |
| | JOB FOR SCOPE OF WORK WILL BE REQUIRED |
| | ON TITLE BLOCKS. |
| | |
| | 6)NOTE: PLEASE SEE 2002 NEC, 210.12 AS |
| | ARC FAULT PROTECTION IS REQUIRED FOR ALL |
| | "OUTLETS" IN SLEEPING RMS. |
| | PLEASE SEE CIRCUIT(S), AS ONE BEDRM |
| | CIRCUIT DOES NOT INDICATE ARC FAULT |
| | PROTECTION, ALTHOUGH A CIRCUIT #16, |
| | DOES, YET THIS CIRCUIT COULD NOT BE |
| | LOCATED ON PLANS OR FOR CIRCUIT FOR |
| | BEDRMS? |
| | PLEASE CORRELATE. |
| | |
| | 7)NOTE: PLEASE SEEMISSING FOOTER STEEL |
| | AS PART OF THE GROUNDING ELECTRODE |
| | SYSTEM. THE FOOTER STEELL IS REQUIRED |
| | PER NEC 250.50,250.52 AND THIS AHJ. |
| | THIS CONNECTION SHALL BE MADE. |
| | |
| | 8)NOTE: PLEASE SEE MISSING SMOKE |
| | DETECTOR ON FIRST FLR LEADING TO THE FLR |
| | ABOVE PER NFPA-72 11.5.1.1 . |
| | |
| | 9)NOTE: PLEASE SEE THAT A MIN OF 10FT |
| | CANDLES (108 LUX) IS REQUIRED UNDER |
| | NORMAL LIGHTING CONDITIONS FOR STAIR |
| | WAY, AND IS PERMITTED TO BE RATED DOWN |
| | TO 1 FT CANDLE MIN UNDER EM CONDITIONS. |
| | LS 1017.8.1.3,7.9.2.2 |
| | |
| | 10)NOTE: PLEASE BE SURE TO COMPLETELY |
| | REMOVE ALL OLD/VOIDED SHEETS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESITONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |