| Plan Review Notes For Permit 06011128 |
| Permit Number |
06011128 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-02-08 00:00:00 | DENIED; | | | 1.FBC-2004 PLUMBING TABLE 403.1 # 2 B. | | | TWO BATHROOMS AND A DRINKING FOUNTAIN | | | ARE REQUIRED. | | | 2.SHOWA SANITARY AND WATER RISER DIAGRAM | | | SEE FBC-2004 CHAPTER 1 SEC. 106.3.5.1.3. | | | 3.FLOOR DRAIN IS NOT VENTED. FLOOR DRAIN | | | DRAIN SHOULD COME OF OF THE LAV. BRANCH. | | | 4.FBC2004 CHAPTER 11, HANDICAP LAV TO BE | | | 5" OFF WALL. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|