Plan Review Notes
Plan Review Notes For Permit 06011125
Permit Number 06011125
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2006-04-21 00:00:00******OK******
  
 1) PLEASE NOTE THAT THE DISTANCE BETWEEN
 THE TWO REQUIRED EXITS SHALL COMPLY WITH
 NFPA 101, SECTION 7.5.1.3.3 WHICH STATES
 THAT "NOT LESS THAN 1/3 THE LENGTH OF
 THE MAXIMUM OVERALL DIAGONAL DIMENSION
 OF THE BUILDING OR AREA TO BE SERVED".
 IT APPEARS THAT THIS DISTANCE WAS
 CALCULATED ON LESS THAN THE ENTIRE AREA.
  
 2) THAT DISTANCE SEPARATION IS STILL
 REQUIRED WHERE MORE THAN (2) EXITS ARE
 PROVIDED IN ACCORDANCE WITH NFPA 101,
 SECTION 7.5.1.3.6.
  
 PLANS SCALED SHOWING COMPLIANCE.
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722