| Plan Review Notes For Permit 06011125 |
| Permit Number |
06011125 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-04-21 00:00:00 | ******OK****** | | | | | | 1) PLEASE NOTE THAT THE DISTANCE BETWEEN | | | THE TWO REQUIRED EXITS SHALL COMPLY WITH | | | NFPA 101, SECTION 7.5.1.3.3 WHICH STATES | | | THAT "NOT LESS THAN 1/3 THE LENGTH OF | | | THE MAXIMUM OVERALL DIAGONAL DIMENSION | | | OF THE BUILDING OR AREA TO BE SERVED". | | | IT APPEARS THAT THIS DISTANCE WAS | | | CALCULATED ON LESS THAN THE ENTIRE AREA. | | | | | | 2) THAT DISTANCE SEPARATION IS STILL | | | REQUIRED WHERE MORE THAN (2) EXITS ARE | | | PROVIDED IN ACCORDANCE WITH NFPA 101, | | | SECTION 7.5.1.3.6. | | | | | | PLANS SCALED SHOWING COMPLIANCE. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|