| 2006-03-02 00:00:00 | **** UNSAT *** |
| | |
| | 1)NOTE: PLEASE SEE MISSING CERTICATE OF |
| | AUTHORIZATION NUMBER FOR MECHNICAL |
| | ENGINEERING FIRM WHICH IS REQUIRED ON |
| | TITLE BLOCK PER FLORIDA ADMINISTRATIVE |
| | CODE 61G15-23.002, FLORIDA STATUES |
| | 481.219. THIS COMMENT IS NOT FOR |
| | ELECTRICAL ENGINEER. |
| | |
| | 2)NOTE: PLEASE VERIFY LOADS FOR TRACK |
| | LIGHTING PER 220.12B , PLEASE SHOW |
| | TOTALS ETC. |
| | PLEASE ALSO SHOW ALL CONTINUOUS LOADS AT |
| | 125%( LIGHTING). 215.3,230.42. |
| | |
| | 3)NOTE: PLEASE CORRELATE LOAD |
| | CALCUALTIONS SUBMITTED WITH RISER |
| | DIAGRAM. PLEASE SEE LOADS INDICATE |
| | SERVICE AS 1000A'S, WHEN RISER SHOWS |
| | 1200A'S? |
| | 215.5 |
| | |
| | 4)NOTE: PLEASE SEE KEYNOTE #8 WHICH |
| | MENTIONS EM LTS TO BE CONNECTED TO EM |
| | CIRCUIT. PLEASE SEE 700.12E WHICH |
| | REQUIRES THE BRANCH CIRCUIT FEEDING THE |
| | UNIT EQUIPMENT SHALL BE THE SAME BRANCH |
| | CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD |
| | OF ANY LOCAL SWITCHES. |
| | PLEASE ADJUST NOTE FOR FIXTURES BEING |
| | ADDED. |
| | |
| | 5)NOTE: PLEASE SEE FBC 2004 CHAPTER 13 , |
| | 13-415.1.ABC.1.2, |
| | PLEASE ALSO SEE 13-415.1.ABC.1.1 WHICH |
| | WILL REQUIRED THE LIGHTING INSIDE ROOMS |
| | TO BE PART OF THE LIGHTING CONTROL |
| | SYSTEM. |
| | |
| | 6)NOTE: PLEASE SEE NOTE ON LV PLANS |
| | MENTIONS WIRING BY OTHERS. PLEASE KNOW, |
| | IF LV IS NOT INCLUDED ONTHIS PERMIT, |
| | THEN SEPARATE PERMIT AND PLANS WILL BE |
| | REQUIRED BEFORE INSTALLATION. |
| | |
| | ** PLEASE SEE ANY COMMENTS FROM OTHER |
| | TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | ** PLEASE BE SURE TO REMOVE ALL |
| | OLD/VOIDED SHEETS FROM SETS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | ONE COPY OF OLD/VOIDED SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |