| Date |
Text |
| 2007-02-03 19:19:48 | *** UNSAT 3RD REVIEW *** |
| | |
| | 1) NOTE: PLEASE SEE PREVIOUS TWO REVIEWS WHICH |
| | REQUESTED ENERGY CALCULATIONS, PERFORMANCE LIGHTING |
| | LEVELS. |
| | PLEASE SEE THE LIGHTING OVER RIDE DEVICES MUST BE |
| | LOCATED AT ENTRANCES OF INGRESS INTO THE BUILDING WHERE |
| | AN OCCUPANT MAY ENTER AFTER HOURS. PLEASE SEE THAT ANY |
| | MANUAL OVER RIDE DEVICE MUST BE READILY ACCESSIBLE. |
| | PLEASE SEE SOME MEANS FOR OVER RIDING LIGHTING AT ALL |
| | LOCATIONS OF ENTRANCE. |
| | PLEASE SEE SOME DEVICES ON PLANS SEEM TO BE SHOWN AS A |
| | STANDARD WALL SWITCH AS INDICATED ON SYMBOL LEGEND. |
| | PLEASE SEE PLANS MENTIONS A TIME CLOCK, HOWEVER IS THIS |
| | A ASTRONOMICAL TC? |
| | |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 |
| | PLEASE SEE THE PLANS SUBMITTED DO NOT CONTAIN THESE. |
| | PLEASE SEE FBC 13-415.1.AB.1, 13-415.2 ETC |
| | |
| | 2) NOTE: PLEASE SEE 210.12 FOR LOADS TO BE FIGURED AND |
| | SHOWN PER 220.12. |
| | PLEASE SEE THE MINIMUM VA PER FT SHALL BE FIGURED FOR |
| | SERVICE/FEEDERS. |
| | PREVIOUS TWO REVIEWS. |
| | |
| | 3) NOTE: PLEASE CLARIFY NOTE ON PLANS WHICH MENTIONS |
| | ALL LIGHTING IS EXISTING. HOW IS THIS POSSIBLE WHEN |
| | THIS IS A NEW BUILD OUT? |
| | |
| | 4) NOTE: PLEASE SEE THE PREVIOUS REVIEW GAVE A NOTICE |
| | TO FS 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS FOR |
| | CODE COMPLIANCE THREE OR MORE TIMES FOR THE SAME |
| | COMMENTS. |
| | PLEASE SEE A FEE OF $1680.00 IS NOW ASSESSED AND WILL |
| | BE REQUIRED TO BE PAID BEFORE NEXT RE-SUBMITTAL. |
| | PLEASE KNOW THIS FEE MAY ALSO BE FOR ANY OTHER TRADE |
| | WHICH MAY HAVE THE SAME COMMENT THREE OR MORE TIMES. |
| | PLEASE SEE BUILDING REVIEW COMMENTS. |
| | |
| | |
| | ** ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |