| 2006-09-19 00:00:00 | ********UNSAT 2ND REVIEW ********* |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED, ALONG |
| | WIHT NEW COMMENTS BASED ON PLANS |
| | SUBMITTED. |
| | PLEASE SEE NOTES BELOW ARE TAKEN |
| | DIRECTLY FROM PREVIOUS REVIEW AND NEW |
| | NOTES ARE ADDED TO THE BOTTOM. |
| | |
| | 1)NOTE: OK. |
| | |
| | 2)NOTE:OK, MOST CODES ADDED, HOWEVER |
| | PLEASE BE SURE THE ELECTRICAL PLANS ALSO |
| | STATE THE 2004 FBC. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASEBE SURE ALL CURRENT |
| | CODES FOR THE FOLLOWING ARE REFERENCED |
| | ON ELECTRICAL PLANS. |
| | 2002 NFPA-70, 2003 NFPA-101, 2002 |
| | NFPA-72. |
| | PLEASE SEE SHEETSWHICH REFLECT THE |
| | 2001 FBC. |
| | PLEASEKNOW, THE STATE OF FLORIDA |
| | ADOPTED THE 2004 FBC ON OCT 1ST, 2005 |
| | |
| | 3)NOTE: OK. |
| | |
| | 4)NOTE:NO, PLEASE VERIFY AS THE |
| | DISONNECT IS BEING NOTED AS BEING FUSED |
| | AND 10K IS NOT COMMEN FOR THE AIC |
| | RATINSGS FOR FUSES. PLEASE SEE NEW |
| | COMMENTS ALSO. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE THE AIC RATINGS |
| | FOR THE NEW FUSES FOR MAINS. 110.9,215.5 |
| | |
| | 5)NOTE: OK. SEE NEW NOTES. |
| | |
| | 6)NOTE: NO, PLEASE SEE NO SYSTEM WAS |
| | SUBMITTED AND SHOWN AS REQUIRED. A TC |
| | NOTED FOR LTS, DOES NOT GIVE ALL |
| | INFORMATION AS NEEDED. PLEASE PROVIDE |
| | THE SYSTEM, SCHEDULING, ALL OVER-RIDES |
| | ETC. PLEASE SEE PLANS DO NOT INDICATE |
| | ANY OVER-RIDE DEVICES, MAX TIMES |
| | PERMITTED ON THE DEVICES WHICH MAY BE |
| | INSTALLED. |
| | PLEASE SEE TAKING THE SECTIONS OF THE |
| | CODE AND QUOTING THE CODE IS NOT |
| | ACCEPTABLE IN LEIU OF MIN DESIGNS |
| | REQUUIRED ON PLANS FOR THE TECHNICAL REQUIREMENTS. |
| | FBC 106.1, ADMIN SECT. |
| | NO ENERGY CALCULATIONS, NO LIGHTING |
| | POWER ALLOWANCES ETC. |
| | PLEASE SEE NOTES BELOW. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE FBC CHAPTER 13, FOR |
| | THE NEW REWUIREMENTS FOR COMMERCIAL |
| | BLDGS. |
| | PLEASE SEE A WORST CASE CALCUALTION TO |
| | BE SHOWN FOR VOTLAGE DROP TO MEET THE |
| | MIN AS SET FORTH IN 13-413.1ABC.1 |
| | PLEASE SEE 13-415.1.ABC.1 & .2 FOR |
| | INTERIOR LIGHTING SHUTOFF, SPACE |
| | LIGHTING CONTROLS REQUIRED.PLEASE |
| | PROVIDE SCHEDULING. |
| | PLEASE SEE 13.415.1.ABC.1.4 FOR EXTERIOR |
| | LTS, AND TYPE OF TIME CLOCK REQUIRED . |
| | PLEASE SEE 13-415.1.ABC.3 TANDEM WIRING. |
| | PLEASE SEE 13-415.1.AB.1 FOR |
| | CALCULATIONS. |
| | |
| | 7)NOTE: OK, HOWEVER SEE LOAD IS SHOWN |
| | BEING DIVIDED BY 208V? PLEASE SEETHIS IS |
| | A 120V CIRCUIT, PLEASE ADJUST. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INDICATE TH REQUIRED SIGN |
| | CIRCUIT PER 600.5.PLEASE KNOW, THIS SIGN |
| | CIORCUIT MAY NOT FEED OTHER AREAS. |
| | |
| | 8)NOTE: OK, HOWEVER PLEASE SEE THESE |
| | LOADS DO NOT CORRELATE WITH THE CIRCUITS |
| | AND LOADS SHOWN ON PANEL SCHEDULES, AND |
| | THE LOADS ARE ALSO SHOWN AT 208V AND NOT |
| | 120V.?? |
| | PLEASE ADJUST. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE VERIFY "SHOW" WINDOW |
| | LIGHTING IS BEING SHOWN AS SIGN |
| | CIRCUITS? |
| | PLEASE SEE 220.12 |
| | |
| | 9)NOTE:NO, PLEASE SEE NOTES ABOVE, AS |
| | THE LOADS WILL CHANGE AND THE LOADS |
| | SHOWN DO NOT INDICATE ALL CONTINOUS |
| | LOADS AT 125%. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT COMPLETE LOAD |
| | CALCULATIONS, AND SHOW ALL CONTINUOUS |
| | LOADS AT 125%. |
| | PLEASE CORRELATE KNOWN RECEPT LOADS WITH |
| | LOADS SHOWN ON PANEL SCHEDULE. |
| | 220.3,220.10,220.11,220.13,215.3,230.42 |
| | ETC |
| | |
| | 10)NOTE: OK, AS THE SERVICE IS BEING |
| | SHOWN AS EXISTING. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE GROUNDING ELECTRODE |
| | SYSTEM, PLEASE PROVIDE DETAIL PER NEC 250.50,250.52. |
| | |
| | 11)NOTE: OK. |
| | |
| | ***** NEW NOTES **** |
| | |
| | 12) NOTE: PLEASE CORRELATE RISER WHICH |
| | INDICATES 350A OCP AND LOAD NOTES |
| | MENTIONS FUSES @ 300A?? |
| | 106.1.2 FBC ADMIN SECT, |
| | |
| | 13) NOTE: PLEASE SEE 700.12E AS THE EM/ |
| | EXT LTS ARE REQUIRED TO BE FED FROM THE |
| | NORMAL BRANCH CIRCUITS FEEDING LOCAL |
| | LIGHTING. |
| | |
| | 14) NOTE: PLEASE SEE THAT NEW ELECTRICAL |
| | PANEL LOCATION SHALL INDICATE THIS AA AN ELECTRICAL |
| | ROOM, NO STORAGE. |
| | 110.26.240.24, 408.7 ETC. |
| | |
| | 15) NOTE: PLEASE SEE FS 553.80(2)(B) |
| | WITH RESPECT TO DESIGN PROFESSIONALS AND |
| | REPEAT CODE COMPLIANT COMMENTS. THIS IS |
| | ONLY GIVEN ANOTICE AT THIS TIME. |
| | |
| | |
| | ** PLEASE SEE ANY OTHER POSSIBLE |
| | COMMENTS FROM OTHER TRADES WHICH MAY |
| | AFFECT ELECTRICAL PLANS. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |