| 2006-03-24 00:00:00 | ******DENIED****** |
| | |
| | 1) CONSTRUCTION, ALTERATION AND |
| | DEMOLITION TO COMPLY WITH NFPA 241. |
| | |
| | 2) LIFE SAFETY SHALL BE IN COMPLIANCE |
| | WITH NFPA 101, 2003 EDITION. |
| | |
| | 3) SHT E-2 ILLUSTRATES FIRE ALARM |
| | DEVICES, AND SHT LS-1 INDICATES THAT |
| | THERE IS NO FIRE ALARM. PLEASE ADVISE |
| | AND MAKE APPROPRIATE CORRECTION. |
| | |
| | 3) WILL THIS PROJECT HAVE IT'S OWN FIRE |
| | ALARM SYSTEM, OR WILL IT BE TIED INTO AN |
| | EXISTING SYSTEM. IF A SEPARATE PANEL IS |
| | INSTALLED, AND THE BUILDING IS FULLY |
| | FIRE SPRINKLERED, THE SYSTEM IS REQUIRED |
| | TO BE UL CERTIFIED FOR CENTRAL STATION |
| | SERVICE. APPROPRIATE DOCUMENTATION WILL |
| | BE REQUIRED PRIOR TO OR AT THE TIME OF |
| | THE FIRE ALARM FINAL INSPECTION. |
| | |
| | 4) SEPARATE SHOP DRAWINGS ARE REQUIRED |
| | FOR FIRE SPRINKLER AND OR FIRE ALARM |
| | SYSTEMS OR REMODEL. |
| | |
| | 5) PLEASE INDICATE THE MINIMUM INTERIOR |
| | FINISH CLASSIFICATION FOR WALLS AND |
| | CEILINGS. |
| | |
| | 6) WHERE PROVIDED AND AS PART OF A FIRE |
| | ALARM SYSTEM, DUCT SMOKE DETECTORS SHALL |
| | INITIATE A GENERAL FIRE ALARM WHEN |
| | ACTIVATED IN ACCORDANCE WITH LOCAL |
| | REQUIREMENTS. |
| | |
| | |
| | MIKE WENNERGREN, CAPTAIN/WPBFR |
| | FIRE PLAN REVIEW (561) 805-6722 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |