| Date |
Text |
| 2006-03-02 00:00:00 | ********UNSAT *********** |
| | |
| | 1)NOTE: PLEASE SEE THE SEAL FOR ENGINEER |
| | STILL CONTAINS THE WORDING OF |
| | "CERTIFICATE". PLEASE KNOW, FAC |
| | 61G1-16.001 WHICH REQUIRED THE WORDING |
| | IN ALL SEALS TO BE CHANGED TO "LICENSE" |
| | PLEASE KNOW THIS RULING BY THE FLORIDA |
| | BOARD OF PROFESSIONAL ENGINEERS WAS |
| | PASSED ON FEB 5, 2004. AN EXTENSION WAS |
| | GRANTED TO THE DATE OF 12/31/05, |
| | WHERE-AS OF JAN 1ST, 2006 SEALS WERE NO |
| | LONGER ACCEPTABLE WITH THE WORDING OF "CERTIFICATE". |
| | PLEASE OBTAIN NEW SEAL. |
| | |
| | 2)NOTE: PLEASEBE SURE ALL CURRENT |
| | CODES FOR THE FOLLOWING ARE REFERENCED |
| | ON ELECTRICAL PLANS. |
| | 2002 NFPA-70, 2003 NFPA-101, 2002 |
| | NFPA-72. |
| | PLEASE SEE SHEETSWHICH REFLECT THE |
| | 2001 FBC. |
| | PLEASEKNOW, THE STATE OF FLORIDA |
| | ADOPTED THE 2004 FBC ON OCT 1ST, 2005 |
| | |
| | 3)NOTE: PLEASE SEE PLANS MENTIONS THE |
| | 2005 NEC. |
| | |
| | 4)NOTE: PLEASE PROVIDE THE AIC RATINGS |
| | FOR THE NEW FUSES FOR MAINS. 110.9,215.5 |
| | |
| | 5)NOTE: PLEASE SHOW ALL PANEL AND |
| | SERVICE LOCATIONS. PLEASE VERIFY IF ALL |
| | MAINS FOR THE ENTIRE BLDG ARE GROUPED. |
| | 230.72 |
| | RISER SHOWS WHAT APPEARS TO BE A SINGLE |
| | METER EXISTING SERVICE WITH NEW MAIN |
| | ADDED?, IS THIS THE SERVICE FOR THE |
| | ENTIRE BLDG? |
| | PLEASE SHOW AND VERIFY THE ENTIRE |
| | SERVICE. |
| | |
| | 6)NOTE: PLEASE SEE FBC CHAPTER 13, FOR |
| | THE NEW REQUIREMENTS FOR COMMERCIAL |
| | BLDGS. |
| | PLEASE SEE A WORST CASE CALCULATION TO |
| | BE SHOWN FOR VOLTAGE DROP TO MEET THE |
| | MIN AS SET FORTH IN 13-413.1ABC.1 |
| | PLEASE SEE 13-415.1.ABC.1 & .2 FOR |
| | INTERIOR LIGHTING SHUTOFF, SPACE |
| | LIGHTING CONTROLS REQUIRED.PLEASE |
| | PROVIDE SCHEDULING. |
| | PLEASE SEE 13.415.1.ABC.1.4 FOR EXTERIOR |
| | LTS, AND TYPE OF TIME CLOCK REQUIRED . |
| | PLEASE SEE 13-415.1.ABC.3 TANDEM WIRING. |
| | PLEASE SEE 13-415.1.AB.1 FOR |
| | CALCULATIONS. |
| | |
| | 7)NOTE: PLEASE INDICATE TH REQUIRED SIGN |
| | CIRCUIT PER 600.5.PLEASE KNOW, THIS SIGN |
| | CIRCUIT MAY NOT FEED OTHER AREAS. |
| | |
| | 8)NOTE: PLEASE VERIFY "SHOW" WINDOW |
| | LIGHTING IS BEING SHOWN AS SIGN |
| | CIRCUITS? |
| | PLEASE SEE 220.12 |
| | |
| | 9)NOTE: PLEASE SUBMIT COMPLETE LOAD |
| | CALCULATIONS, AND SHOW ALL CONTINUOUS |
| | LOADS AT 125%. |
| | PLEASE CORRELATE KNOWN RECEPT LOADS WITH |
| | LOADS SHOWN ON PANEL SCHEDULE. |
| | 220.3,220.10,220.11,220.13,215.3,230.42 |
| | ETC |
| | |
| | 10)NOTE: PLEASE SEE GROUNDING ELECTRODE |
| | SYSTEM, PLEASE PROVIDE DETAIL PER NEC 250.50,250.52. |
| | |
| | 11)NOTE: PLEASE PROVIDE ROOM AND ARE |
| | DESIGNATIONS ON PLANS. |
| | |
| | ** PLEASE SEE ANY OTHER POSSIBLE |
| | COMMENTS FROM OTHER TRADES WHICH MAY |
| | AFFECT ELECTRICAL PLANS. |
| | |
| | |
| | ** PLEASE COMPLETETLY REMOVED ANY |
| | OLD/VOIDED SHEETS FROM SETS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO TWO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| 2006-03-01 00:00:00 | IN ELEC FOR REVIEW |