| 2006-10-05 00:00:00 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | | | | FROM PREVIOUS REVIEW: COMMENT NUMBER TO | | | REMAIN THE SAME. | | | | | | 9. SHT A-2 SUBMIT CALCULATIONS FOR THE | | | PRIMARY AND SECONDARY ROOF DRAINS PER | | | SECTION 1106 & 1107 WITH ALL | | | SUBSECTIONS. SHOW THE SF AREA OF THE | | | ROOF, WITH 1/2 AREA OF ALL VERTICAL | | | WALLS INCLUDING PARAPETS ADDED TO THE SF | | | OF THE ROOF AS WELL AS THE AREA OF ALL | | | ROOFS THAT DRAIN ONTO THE ROOF FROM | | | ABOVE, (IF ANY). | | | ***RESPONSE NOTED, BUT CALCULATIONS | | | INDICATE A TOTAL OF 2,545SF. SHT A-1 | | | INDICATES NEW RETAIL 2,640SF. ALSO NO | | | INFORMATION FOR THE VERTICAL WALLS | | | ADJACENT TO THE ROOF FROM THE OTHER | | | SPACES IN THE BUILDING. NORTH ELEVATION | | | ON SHT A-2 INDICATES THE TOP OF THE | | | PARAPET TO BE 29'0", AND THE TOP OF THE | | | PARAPET TO THE SOUTH IS 16'0". NO | | | CONTRIBUTION FROM THE VERTICAL WALLS WAS | | | INDICATED IN THE CALCULATIONS. ALSO | | | PLEASE INDICATE THE ELEVATION FOR THE | | | ROOF AT BOTH THE HIGH END AND THE LOW | | | END TO VERIFY CALCULATIONS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-7631 | | | E-MAIL [email protected] |
|