| 2006-04-24 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 06011121 |
| | ADD: 2100 45TH ST. SUITE# |
| | CONT: ITASCA CONSTRUCTION |
| | TEL: (561)241-4999 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) PLEASE PROVIDE WHAT SUITE NUMBER |
| | WORK WILL COVER UNDER THIS PERMIT. |
| | |
| | 1B) SHEET SP-1 INDICATES NOTES TO |
| | PROVIDE CURB CUTS AND HANDICAPPED CCESS |
| | AISLES ALONG FRONTAGE OF BUILDING |
| | ,ISTHIS ALSO COVERED UNDER THIS PERMIT? |
| | |
| | 1C) SHEET SP-1 ALSO INDICATES ALONG 45TH |
| | STREET THE DRIVE APPROACH FOR THIS |
| | PROPERTY BEING WIDENED, IS THIS WORK |
| | ALSO TO BE INCLUDED UNDER THIS PERMIT? |
| | |
| | 2A) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 2B) THE WRONG OWNER INFORMATION IS |
| | LISTED ON THE PERMIT APPLICATION. IF |
| | RECENTLY SOLD PROVIDE UPDATED |
| | INFORMATION FOR OWNERSHIP, OTHERWISE |
| | CORRECT PERMIT APPLICATION TO MATCH NOC. |
| | |
| | 3) 109.3.10.1 HURICANE PROTECTION. |
| | IT SHALL BE UNLAWFUL FOR ANY PERSON TO |
| | ALLOW CONSTRUCTION RELATED MATERIALS |
| | EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR |
| | OTHERWISE UNSECURED AT A CONSTRUCTION |
| | SITE FROM 24 HRS. AFTER A HURRICANE |
| | WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN |
| | LIFTED. ALL SUCH CONSTRUCTION MATERIALS, |
| | EQUIPMENT AND DEBRIS SHALL BE EITHER |
| | REMOVED FROM THE CONSTRUCTION SITE OR |
| | SECURED IN SUCH A MANNER AS TO MINIMIZE |
| | THE DANGER OF SUCH CONSTRUCTION |
| | MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM |
| | HIGHWINDS. |
| | ANY PERSONS WHO FAILS TO COMPLY TO |
| | REMOVE OR SECURE THE CONSTRUCTION |
| | MATERIALS EQUIPMENT AND DEBRIS WITHIN |
| | 24 HRS AFTER A HURRICANE WATCH HAS BEEN |
| | ISSUED SHALL BE SUBJECT TO A FINE NOT TO |
| | EXCEED $500.00. |
| | IN ADDITION TO THE ABOVE, A LICENSED |
| | CONTRACTOR WHO VIOLATES THIS SECTION |
| | SHALL BE SUBJECT TO DISCIPLINE PURSUANT |
| | TO SECTION 113 OF THIS CHAPTER. |
| | |
| | 4) 109.3.10* IMPACT OF CONSTRUCTION. ALL |
| | CONSTRUCTION ACTIVITY REGULATED BY THIS |
| | CODE SHALL BE PERMORMED IN A MANNER SO |
| | AS NOT TO ADVERSLY IMPACT THE CONDITION |
| | OF ADJACENT PROPERTY, UNLESS SUCH |
| | ACTIVITY IS PERMITTED TO AFFECT SAID |
| | PROPERTY PURSUANT TO A CONSENT BY THE |
| | APPLICABLE PROPERTY OWNER, UNDER TERMS & |
| | CONDITIONS AGREEABLE TO THE APPLICABLE |
| | PROPERTY OWNER.THIS INCLUDES BUT IS NOT |
| | LIMITED TO THE CONTROL OF DUST, NOISE, |
| | WATER OR DRAINAGE RUN-OFF, DEBRIS, AND |
| | THE STORAGE OF CONSTRUCTION MATERIALS. |
| | NEW CONSTRUCTION ACTIVITY SHALL NOT |
| | ADVERSELY IMPACT HISTORICSURFACE WATER |
| | DRAINAGE FLOWS SERVING ADJACENT |
| | PROPERTIES, & MAY REQUIRE SPECIAL |
| | DRAINAGE DESIGNCOMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED |
| | SITES.ACCORDINGLY, DEVELOPERS, |
| | CONTRACTORS, AND OWNERS OF ALL NEW |
| | RESIDENTIAL DEVELOPMENET, INCLUDING |
| | ADDITIONS, POOLS, PATIOS, DRIVEWAYS, |
| | DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN |
| | EXCESS OF 800SQ FT OF PERMEABLE LAND |
| | AREA ON ANY PARCELL SHALL AS A PERMIT |
| | CONDITION, PROVIDE A PROFESSIONALY |
| | PREPARED DRAINAGE PLAN CLEARLY |
| | INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE |
| | IMPROVEMENT, A CERTIFICATE FROM A |
| | LICENSED ENGINEER SHALL BE SUBMITTED TO |
| | THE INSPECTOR IN ORDER TO RECEIVE |
| | APPROVAL OF THE FINAL INSPECTION. |
| | |
| | 5) 110.2* W. P. B. ADMINISTRATIVE CODE, |
| | INFORMATION THAT IS REQUIRED FOR RECORD |
| | KEEPING & FOR CERTIFICATE OF OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PERMIT WAS ISSUED (2004). |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT. |
| | ------------------------------------- |
| | G ) SQ. FT. PER FL |
| | H ) SQ. FT. FOOTPRINT |
| | I ) SQ. FT. UNDER ROOF (TOTAL) |
| | J ) OCCUPANT LOAD |
| | K ) FLOOD ZONE |
| | L ) FLOOD ELEVATION |
| | M) WHAT USAGE CLASSIFICATION TO BE USED |
| | FOR ON THE 2ND FLOOR? |
| | |
| | 6) WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 7)1609.1.4 PROTECTION OF OPENINGS. |
| | IN WIND-BORNE DEBRIS REGIONS, EXTERIOR |
| | GLAZING THAT RECEIVES POSITIVE PRESSURE |
| | IN THE LOWER 60 FEET (18.3 M) IN |
| | BUILDINGS SHALL BE ASSUMED TO BE |
| | OPENINGS AND THE BALANCE OF GLAZED |
| | OPENINGS IN THE REST OF THE BUILDING |
| | SHALL BE ASSUMED TO BE ZERO UNLESS SUCH |
| | GLAZING THAT RECEIVES POSITIVE PRESSURE |
| | IS IMPACT RESISTANT OR PROTECTED WITH AN |
| | IMPACT RESISTANT COVERING MEETING THE |
| | REQUIREMENTS OF SSTD 12, ASTM E 1886 AND |
| | ASTM E 1996, OR MIAMI-DADE TAS 201, 202 |
| | AND 203 REFERENCED THEREIN AS FOLLOWS: |
| | 1.GLAZED OPENINGS LOCATED WITHIN 30 |
| | FEET (9.1 M) OF GRADE SHALL MEET THE |
| | REQUIREMENTS OF THE LARGE MISSILE TEST. |
| | 2.GLAZED OPENINGS LOCATED MORE THAN |
| | 30 FEET (9.1 M) ABOVE GRADE SHALL MEET |
| | THE PROVISIONS OF THE SMALL MISSILE |
| | TEST. |
| | |
| | 8) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) WINDOWS |
| | B) MULLIONS IF NOT PART OF WINDOW |
| | REPORT |
| | C) GLASS DOORS |
| | D)STORM SHUTTERS |
| | E) ROOFING ASSEMBLIES. |
| | |
| | 9) PRODUCT APPROVALS SUBMITED ARE FOR |
| | BOTH LARGE AND REPORTS FOR |
| | SMALL MISSLE IMPACT GLAZING. GLAZED |
| | OPENINGS ZERO -30 FT REQUIRE LARGE |
| | MISSLE IMPACT GLAZING, OR SHUTTERS. |
| | SINCE THIS IS CONDOS AND A LARGE PROJECT |
| | IF SHUTTERS ARE TO BE USED APPROVAL FROM |
| | THE BUILDING OFFIICAL WILL BE REQUIRED. |
| | SEE THE BUILDING OFFICIALS |
| | INTERPRETATION OF CODE. SEE QUESTION 13 |
| | & 14 OF INTERPRETATION OF STANDARDS. |
| | **************************** |
| | (13) RECOGNIZING SUCH CONCERNS AS |
| | ABSENTEE OWNERS, OR CASES WHERE LONGER |
| | TIME & EFFORT IS NECESSARY TO SECURE |
| | SHUTTERS ON LARGE OR MULTI-STORY |
| | BUILDINGS, WHAT MEASURES ARE BEING |
| | RECOMMENDED OR IMPLEMENTED TO ENSURE |
| | THAT COMPLETE INSTALLATION OR SECURING |
| | IS DONE SUFFICIENTLY IN ADVANCE OF THE |
| | HURRICANE EVENT? |
| | (13) ANSWER: IN MATTERS CONCERNING |
| | PUBLIC SAFETY, HEALTH, AND THE GENERAL |
| | WELFARE NOT SPECIFICALLY ADDRESSED IN |
| | THE CODE SECTION 104.1* FLORIDA BUILDING |
| | CODE, 2004 EDITION, PROVIDES THE ABILITY |
| | FOR THE BUILDING OFFICIAL TO IMPLEMENT |
| | REQUIREMENTS FOR ENSURING STABILITY, |
| | STRENGTH, AND PROPER OPERATION OF |
| | EXISTING & NEW BUILDINGS. |
| | IN ORDER TO ASSURE THE SECURING OF |
| | SHUTTERS ON LARGE OR MULTI-STORY |
| | BUILDING, OR MULTIPLE BUILDINGS ON THE |
| | SAME PROPERTY, PRE-STORM PREPARATION |
| | PLANS MUST BE SUBMITTED BY THE PROPERTY |
| | OWNERS OR MANAGING AGENTS FOR REVIEW BY |
| | THE CONSTRUCTION SERVICES DEPARTMENT. |
| | ANY SUCH PLAN SHALL INCLUDE, AT A |
| | MINIMUM, ON-SITE LOCATION OF SHUTTERS, |
| | PARTY RESPONSIBLE FOR SECURING THE |
| | SHUTTERS (SAID PARTIES MUST BE LOCATED |
| | WITHIN PALM BEACH COUNTY), TOTAL NUMBER |
| | OF OPENINGS TO BE PROTECTED AND TOTAL |
| | TIME REQUIRED TO SECURE ALL OPENINGS. |
| | PROTECTION OF OPENINGS SHALL BE |
| | ACCOMPLISHED WITHIN TWELVE (12) HOURS OR |
| | LESS OF THE OFFICIAL NOTIFICATION BY THE |
| | NATIONAL WEATHER SERVICE OF A HURRICANE |
| | WATCH. |
| | PROVISIONS IN THE BUILDING CODES |
| | (AND THIS STANDARD) ARE NOT INTENDED TO |
| | PROHIBIT THE USE OF ALTERNATIVE |
| | MATERIALS AND METHODS, AND ALLOW THE |
| | BUILDING OFFICIAL TO REVIEW AND APPROVE |
| | ANY ALTERNATE DEEMED EQUIVALENT IN |
| | QUALITY, STRENGTH, EFFECTIVENESS, FIRE |
| | RESISTANCE, DURABILITY AND SAFETY |
| | PRESCRIBED BY CODE. BASED UPON THIS CODE |
| | PROVISION, ACCEPTANCE OF ALTERNATE |
| | MATERIALS AND METHODS MAY BE APPROVED ON |
| | A CASE-BY-CASE BASIS AND SHALL REQUIRE |
| | SUFFICIENT EVIDENCE OR PROOF TO |
| | SUBSTANTIATE ANY CLAIM MADE REGARDING |
| | THE ALTERNATE. |
| | |
| | (14)ARE REMOVABLE STORM PANELS |
| | APPROPRIATE FOR USE ON VERY LARGE, MID |
| | OR HIGH-RISE STRUCTURES? |
| | (14) ANSWERS: NO, EXCEPT ON THE |
| | GROUND FLOOR. ON COMMERCIAL AND |
| | MULTI-UNIT RESIDENTIAL STRUCTURES, ABOVE |
| | THE FIRST LEVEL, IMPACT RESISTANT |
| | GLAZING OR PERMANENTLY AFFIXED |
| | PROTECTIVE DEVICES SHALL BE INSTALLED. |
| | PERMANENTLY AFFIXED PROTECTIVE DEVICES |
| | SHALL REQUIRE THE WRITTEN APPROVAL OF |
| | THE BUILDING OFFICIAL. |
| | ************************** |
| | 10) 2004 FL. BLD CODE 1603.1.4 THE |
| | FOLLOWING INFORMATION RELATED TO WIND |
| | SHALL BE SHOWN ON THE CONSTRUCTION |
| | DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | ASCE7-95 WRONG WIND DESIGN, 2004 FBC |
| | USES ASCE7 -02. |
| | |
| | 11)S-1 |
| | 11A) UPDATE BUILDING CODE TO 2004 FBC |
| | BUILDING, 2004 EXISTING BUILDING CODE. |
| | |
| | 11B) UPDATE ACI-95 TO ACI- 315-02 |
| | |
| | 11C) STRUCTURAL NOTES (H) REFERS TO SFBC |
| | 2404.2 CORRECT TO 1802.2.1 QUESTIONABLE |
| | SOIL. |
| | WHERE THE SAFE-SUSTAINING POWER OF THE |
| | SOIL IS IN DOUBT, OR WHERE A |
| | LOAD-BEARING VALUE SUPERIOR TO THAT |
| | SPECIFIED IN THIS CODE IS CLAIMED, THE |
| | BUILDING OFFICIAL SHALL REQUIRE THAT THE |
| | NECESSARY INVESTIGATION BE MADE. SUCH |
| | INVESTIGATION SHALL COMPLY WITH THE |
| | PROVISIONS OF SECTIONS 1802.4 THROUGH |
| | 1802.6 . |
| | PROVIDE SOILS REPORT, ORIGINAL 2 SETS. |
| | |
| | 12) EXISTING BUILDING CODE 2004, 902.2 |
| | AREA LIMITATION. NO ADDITION SHALL |
| | INCREASE THE AREA OF AN EXISTING |
| | BUILDING BEYOND THAT PERMITTED UNDER THE |
| | APPLICABLE PROVISIONS OF CHAPTER 5. |
| | |
| | 13) 13-101.1.2 ADDITIONS. |
| | ADDITIONS TO EXISTING COMMERCIAL |
| | BUILDINGS ARE CONSIDERED NEW BUILDING |
| | CONSTRUCTION AND SHALL COMPLY WITH |
| | SUBCHAPTER 13-4 OF THIS CODE AS ALLOWED |
| | IN SECTION 101.1.1 . |
| | ADDITIONS TO EXISTING NONRESIDENTIAL |
| | BUILDINGS THAT ARE UNABLE TO COMPLY WITH |
| | CODE REQUIREMENTS FOR THE ADDITION ALONE |
| | MAY COMPLY WITH THE CODE BY BRINGING THE |
| | ENTIRE BUILDING INTO COMPLIANCE WITH THE |
| | REQUIREMENTS FOR NEW BUILDINGS. |
| | |
| | 13-101.1.3 RENOVATIONS. |
| | RENOVATED COMMERCIAL BUILDINGS SHALL, |
| | WHEN APPLICABLE (SEE SECTION 202 ), |
| | COMPLY WITH THE PRESCRIPTIVE |
| | REQUIREMENTS CONTAINED IN FORM 400 C OR |
| | WITH METHOD B OF SUBCHAPTER 13-4 FOR |
| | INSULATION, HVAC SYSTEMS, LIGHTING, |
| | WATER HEATING SYSTEMS AND EXTERIOR |
| | ENVELOPE COMPONENTS BEING RETROFITTED OR |
| | REPLACED. |
| | |
| | 14) LS-1 NO EXIT LIGHTS OR EMERGENCY |
| | LIGHTING PROVIDED. |
| | |
| | 15) BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |