Plan Review Notes
Plan Review Notes For Permit 06011074
Permit Number 06011074
Review Stop E
Sequence Number 1
Notes
Date Text
2006-02-22 00:00:00MASTER PERMIT SHOWS NO ELECTRIC FOR CAR
 WASH PLEASE SUBMIT RISER DIAGRAM AND
 SHOW WHERE POWER COMES FROM AND
 LOCATIONS OF PANELS.
  
 YOUR PAPER WORK SUBMITTED SHOW 460 VOLT
 POWER FOR THE CAR WASH,PLANS FOR
 BUILDING SHOW 120/208.
  
 IF POWER RISER AND CIRCUIT NUMBERS ARE
 SHOWN ON ANOTHER DRAWING PLEASE
 REFERENCE THOSE PERMIT NUMBERS AND PAGES
 THAT THE INFORMATION CAN BE FOUND ON.
  
  