| 2006-06-29 00:00:00 | ********** UNSAT 2ND REVIEW ************ |
| | |
| | ** PLEASE SEE THE FOLLOWING NOTES AS ALL |
| | INFORMATION NEEDED WAS NOT SUBMITTED. |
| | |
| | ** PLEASE SEE SOME OF THE SAME NOTES |
| | FROM PREVIOUS REVIEW STILL APPLY. |
| | PLEASE SEE NOTES BELOW ARE TAKEN |
| | DIRECTLY FROM PREVIOUS REVIEW. |
| | |
| | |
| | 1)NOTE: OK |
| | |
| | 2)NOTE: OK. |
| | |
| | 3)NOTE: NO, PLEASE SEE AN OLD SITE PLAN |
| | WAS SUBMITTED, HOWEVER LOCATION OF |
| | GENERATOR ETC WAS NOT SHOWN WITH THE NEW |
| | ELEVATION OF GEN ETC. |
| | "SLOSH" ELEVATION IS NOT REQUIRED , |
| | HOWEVER 6" ABOVE BFE WILL BE REQUIRED. |
| | |
| | ** PREVIOUS NOTES ** |
| | PLEASE KNOW, A SITE SURVEY AND |
| | ELEVATIONS WERE NOT SUBMITTED FOR |
| | LOCATION OF GENERATOR AND BFE. |
| | PLEASE SEE LOCATIONS OF GEN IN |
| | NFPA-110,7.2.3* WHICH REFERENCES THE |
| | "SLOSH" CHARTS. |
| | |
| | 4)NOTE: NO, PLEASE SEE NO SPECS ETC WERE |
| | SUBMITTED AND ARE REQUIRED AT THIS TIME. |
| | PLEASE KNOW, IF THE EQUIPMENT HAS NOT |
| | BEEN PURCHASED, PICK ONE , IT ONLY NEEDS |
| | TOMEET ALL LISTINGS BY A NRTL, AND TO |
| | CORRELATE WITH ALL THE CODE REQUIREMENTS |
| | FOR INSTALLATION ETC. **THE EQUIPMENT |
| | CAN BE REVISED AT A LATER DATE IF |
| | DIFFERENT EQUIPMENT IS CHOSEN. |
| | |
| | **PREVIOUS NOTE ** |
| | PLEASE SUBMIT ALL THE |
| | MANUFACTURE'S CUT/SPEC SHEETS FOR |
| | GENERATOR, ATS, AND ANY NEW FUEL |
| | TANK(S). PLEASE BE SURE ALL SPECS/SHEETS |
| | CONTAIN LISTINGS FROM A NRTL. |
| | 215.5 |
| | |
| | 5)NOTE: NO, PLEASE SEE MOST HAS BEEN |
| | CLEARED UP, HOWEVER PLEASE SEE RISER AND |
| | NOTES ON E-1, AS NOTES #4 AND #7, SEEM |
| | TO BE CROSSED.?? |
| | PLEASE SEE NO SIZES ARE PROVIDED FOR NEW |
| | MAIN, ATS ETC. |
| | |
| | ** PREVIOUS NOTE** |
| | PLEASE CORRELATE RISER ON E-1, |
| | WITH RISER ON E-2. |
| | PLEASE SEE NOTE #7 WHICH MENTIONS NEW |
| | CONDUITS FROM NEW MAIN, HOWEVER RISER |
| | SHOWS THIS AS EXIST TO REMAIN AND IS |
| | ALSO NOTED AS EXIST?? |
| | PLEASE SEE NOTE #3, WHICH SHOWS THIS |
| | NOTE FOR WHAT APPEARS TO BE A METER |
| | BEING REMOVED AND MAIN DISCONNECT? |
| | (MISPRINT?) |
| | PLEASE SEE RISER, AS SHOWN SEEMS TO BE |
| | MISPRINTED BACKWARDS ,?? |
| | |
| | 6)NOTE: OK, HOWEVER PLEASE LIST |
| | EQUIPMENT WHICH IS LOCATED IN MAIN |
| | ELECTRICAL RM AS EXISTING WHERE |
| | APPLICABLE. |
| | |
| | 7)NOTE: OK. |
| | |
| | 8)NOTE: NO, PLEASE SEE VALUE WAS NOT |
| | ADJUSTED. PLEASE KNOW, A VALUE WILL BE |
| | PLACED ON THE SCOPE OF WORK BY SUING THE |
| | "MARSHALL'S/ SWIFT" GUIDE IF NOT |
| | INCREASED. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE 2004 FBC 108.3 CITY |
| | OF WEST PALM BEACH ADMINISTRATIVE CODE |
| | WHICH REQUIRES VALUE FOR SCOPE OF |
| | WORK/IMPROVEMENT TO INCLUDE ALL LABOR |
| | AND MATERIALS, EVEN IF EQUIPMENT IS |
| | OWNER SUPPLIED. |
| | PLEASE SEE VALUE IS TOO LOW FOR SCOPE OF |
| | WORK. |
| | |
| | 9)NOTE:NO, PLEASE SEE NO SLAB PLANS, |
| | DETAILS ETC WERE SUBMITTED AND ARE |
| | REQUIRED. |
| | |
| | ** PREVIOUS NOTE** |
| | PLEASE SEE BLDG REVIEW COMMENTS |
| | AS NO SLAB DETAIL WAS SUBMITTED. PLEASE |
| | SEE MIN REQUIREMENTS IN NFPA-110 AND |
| | ENGINEERING PRACTICES FOR A GENERATOR OF |
| | THIS SIZE AND WEIGHT. |
| | 7.2.1.1,7.4, 7.5* |
| | |
| | ** NEW NOTE ** |
| | |
| | 10) NOTE: PLEASE SEE FS 553.80(2)(B) |
| | WITH RESPECT TO REPEAT COMMENTS. |
| | |
| | |
| | ** PLEASE SEE POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | ** PLEASE BE SURE TO REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |