| 2006-02-28 00:00:00 | *********** UNSAT ************ |
| | |
| | ** PLEASE SEE THE FOLLOWING NOTES AS ALL |
| | INFORMATION NEEDED WAS NOT SUBMITTED. |
| | |
| | |
| | 1)NOTE: PLEASE KNOW, THE ADDRESS AND |
| | SITE BE ON TITLE BLOCK OF PLANS. PLEASE |
| | KNOW, THE ADDRESS IS 951 OKEECHOBEE RD, |
| | AND NOT "OLD" OKEECHOBEE AS ON PERMIT |
| | APPLICATION. |
| | |
| | 2)NOTE: PLEASE REFERENCE ALL CURRENTS |
| | CODES FOR INSTALLATION OF THIS PROJECT. |
| | PLEASE SEE 2003 NFPA-101, 2002 NFPA-110, |
| | NFPA-70 2002. |
| | |
| | 3)NOTE: PLEASE KNOW, A SITE SURVEY AND |
| | ELEVATIONS WERE NOT SUBMITTED FOR |
| | LOCATION OF GENERATOR AND BFE. |
| | PLEASE SEE LOCATIONS OF GEN IN |
| | NFPA-110,7.2.3* WHICH REFERENCES THE |
| | "SLOSH" CHARTS. |
| | |
| | 4)NOTE: PLEASE SUBMIT ALL THE |
| | MANUFACTURE'S CUT/SPEC SHEETS FOR |
| | GENERATOR, ATS, AND ANY NEW FUEL |
| | TANK(S). PLEASE BE SURE ALL SPECS/SHEETS |
| | CONTAIN LISTINGS FROM A NRTL. |
| | 215.5 |
| | |
| | 5)NOTE: PLEASE CORRELATE RISER ON E-1, |
| | WITH RISER ON E-2. |
| | PLEASE SEE NOTE #7 WHICH MENTIONS NEW |
| | CONDUITS FROM NEW MAIN, HOWEVER RISER |
| | SHOWS THIS AS EXIST TO REMAIN AND IS |
| | ALSO NOTED AS EXIST?? |
| | PLEASE SEE NOTE #3, WHICH SHOWS THIS |
| | NOTE FOR WHAT APPEARS TO BE A METER |
| | BEING REMOVED AND MAIN DISCONNECT? |
| | (MISPRINT?) |
| | PLEASE SEE RISER, AS SHOWN SEEMS TO BE |
| | MISPRINTED BACKWARDS ,?? |
| | |
| | 6)NOTE: PLEASE SEE EXISTING RISER SHOWS |
| | A EXISTING GEN DISC LCOATED INSIDE, |
| | NOTED TO BE REMOVED, YET NEW REVISED |
| | RISER SHOWS THIS DISCONNECT STILL |
| | LOCATED ON REVISED RISER? PLEASE |
| | CLARIFY, IF THE GEN DISC LOCATED INSIDE |
| | BLDG, IS BEING REMOVED. ALL ELECTRICAL |
| | EQUIPMENT NO LONGER IN USE SHOULD BE |
| | REMOVED. |
| | |
| | 7)NOTE: PLEASE PROVIDE OCP AT GENERATOR, |
| | PLEASE ALSO SEE 445.13. |
| | UNABLE TO VERIFY FEEDER SIZES, ETC . |
| | 215.5 |
| | |
| | |
| | 8)NOTE: PLEASE SEE 2004 FBC 108.3 CITY |
| | OF WEST PALM BEACH ADMINISTRATIVE CODE |
| | WHICH REQUIRES VALUE FOR SCOPE OF |
| | WORK/IMPROVEMENT TO INCLUDE ALL LABOR |
| | AND MATERIALS, EVEN IF EQUIPMENT IS |
| | OWNER SUPPLIED. |
| | PLEASE SEE VALUE IS TOO LOW FOR SCOPE OF |
| | WORK. |
| | |
| | 9)NOTE: PLEASE SEE BLDG REVIEW COMMENTS |
| | AS NO SLAB DETAIL WAS SUBMITTED. PLEASE |
| | SEE MIN REQUIREMENTS IN NFPA-110 AND |
| | ENGINEERING PRACTICES FOR A GENERATOR OF |
| | THIS SIZE AND WEIGHT. |
| | 7.2.1.1,7.4, 7.5* |
| | |
| | ** PLEASE SEE POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | ** PLEASE BE SURE TO REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |