Plan Review Notes
Plan Review Notes For Permit 06011056
Permit Number 06011056
Review Stop P
Sequence Number 1
Notes
Date Text
2006-02-04 00:00:00 
  
  
 PLUMBING PLAN REVIEW EXAMINER
 PAUL SCHMITZ 561-805-6692
 [email protected]
 FBC PLUMBING 2004
 FBC FUEL GAS 2004
 FBC 2004 BUILDING CH 11
 DENIED
 1)CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED
 BY THE BUILDING OFFICAL. CONSTRUCTION
 DOUCMENTS SHALL BE OF SUFFICENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT ITWILL CONFORM TOTHE
 PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS
 AS DETERMINED BY THE BUILDING OFFICAL (
 SEE ALSO SECTION 106.3.5)
  
 2) SHT A-2 BREAK ROOM, REFERENCE TO SHT
 A-1 DETAIL 2,
 SHT A-1 NOT WITH SUBMITTED PLANS.
 NOTE: COMPLY WITH ADA REQUIRMENTS IS NOT
 ACCEPTABLE.PROVIDE ELEVATION DETAIL
 11-4.24 SINKS.
 ?11-4.24.1 GENERAL. SINKS REQUIRED TO
 BE ACCESSIBLE BY ?11-4.1 SHALL
 COMPLY WITH ?11-4.24.
 ?11-4.24.2 HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER OR RIM NO
 HIGHER THAN 34 IN. (865 MM) ABOVE THE
 FINISH FLOOR.
 ?11-4.24.3 KNEE CLEARANCE. KNEE
 CLEARANCE THAT IS AT LEAST 27 IN. (685
 MM) HIGH, 30 IN. (760 MM) WIDE, AND 19
 IN (485 MM) DEEP SHALL BE
 PROVIDED UNDERNEATH SINKS.
 ?11-4.24.4 DEPTH. EACH SINK SHALL BE A
 MAXIMUM OF 6-1/2 IN (165 MM)
 DEEP.
 ?11-4.24.5 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE AT LEAST 30 IN. BY 48
 IN. (760 MM BY 1220 MM) COMPLYING WITH
 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD
 APPROACH.THE CLEAR FLOOR SPACE SHALL
 BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 IN. (485 MM)
 UNDERNEATH THE SINK (SEE FIGURE
 11-32).
 ?11-4.24.6 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED
 UNDER SINKS SHALL BE INSULATED OR
 OTHERWISE CONFIGURED SO AS TO PROTECT
 AGAINST CONTACT.THERE SHALL BE NO
 SHARP OR ABRASIVE SURFACES UNDER
 SINKS.
 ?11-4.24.7 FAUCETS. FAUCETS SHALL
 COMPLY WITH ?11-4.27.4.LEVER-
 OPERATED, PUSH-TYPE, TOUCH-TYPE, OR
 ELECTRONICALLY CONTROLLED MECHANISMS
 ARE ACCEPTABLE DESIGNS.
 3) SHT A-2,SEC 106.3.5.1.3 (4.)
 COMMERICAL BUILDINGS,
 PLUMBING SANITARY DRAINAGE.
 ( DWV ISOMETRIC REQUIRED )
 END OF COMMENTS, QUESTIONS 561-805-6692
  
  
  
  
  
  