| 2006-02-07 00:00:00 | 1) 108.3 BUILDING PERMIT VALUATION. IF |
| | IN THE OPINION OF THE BUILDING OFFICIAL |
| | THE CLAIMED VALUATION OF BUILDING, AL- |
| | TERATION, STRUCTURE, ELECTRICAL, GAS, |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| | TO BE UNDERESTIMATED ON THE APPLICATION, |
| | THE PERMIT SHALL BE DENIED. FOR |
| | PERMITTING PURPOSES, VALUATION FOR |
| | BUILDINGS AND |
| | SYSTEMS SHALL BE FOUND IN MARSHALL AND |
| | SWIFT OR THE SOUTHERN BUILDING CODE |
| | CONGRESS INTERNATIONAL VALUATION TABLES, |
| | LATEST EDITION, AND SHALL BE BASED ON |
| | TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRIC, PLUMBING, |
| | MECHANICAL, INTERIOR FINISH, NORMAL SITE |
| | WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN |
| | FEES, OVERHEAD AND PROFIT, EXCLUDING |
| | ONLY LAND VALUE. VALUATION REFERENCES |
| | MAY INCLUDE THE LATEST PUBLISHED DATA OF |
| | NATIONAL CONSTRUCTION COST ANALYSIS |
| | SERVICES (MARSHALL-SWIFT,MEANS,ETC.) |
| | WITH REGIONAL ADJUSTMENTS FOR LOCATION |
| | AS PUBLISHED BY INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 2) (2004 FBC) 11-4.13.6 MANEUVERING |
| | CLEARANCES AT DOORS. MINIMUM MANEUVERING |
| | CLEARANCES AT DOORS THAT ARE NOT |
| | AUTOMATIC OR POWER-ASSISTED SHALL BE AS |
| | SHOWN IN FIGURE 11-25. THE FLOOR OR |
| | GROUND AREA WITHIN THE REQUIRED |
| | CLEARANCES SHALL BE LEVEL AND CLEAR. |
| | |
| | 3) SHOW IN DETAIL HOW THE SINK WILL MEET |
| | THE ADA REQUIREMENTS. MAKING THE |
| | STATEMENT IS NOT SUFFICENT INFORMATION. |
| | ALL DIMENTIONS AND DRAWINGS SHOWING HOW |
| | THE SINK WILL MEET THE REQUIREMENTS IS |
| | REQUIRED ON THE DRAWINGS. |
| | |
| | 4)(2004 FBC) 106.1.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. CONSTRUCTION |
| | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE & |
| | EXTENT OF THE WORK PROPOSED & SHOW IN |
| | DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND REVELENT |
| | LAWS, ORDINANCES, AND RULES AND |
| | REGULATIONS AS DETERMINED BY THE |
| | BUILDING OFFICIAL. |
| | |