| Plan Review Notes For Permit 06011055 |
| Permit Number |
06011055 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-03-10 08:05:09 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | | | | FROM PREVIOUS REVIEWS: | | | | | | A. SHOW COMPLIANCE FOR THE FOLLOWING: | | | -FOR THE URINAL: | | | 1. 11-4.18.2HEIGHT | | | 2. 11-4.18.3 CLEAR FLOOR SPACE | | | 3. 11-4.18.4 FLUSH CONTROLS | | | -FOR THE LAVS: | | | 1. 11-4.19.2 CLEARANCE SHOWN AS 28" BUT 29" REQUIRED | | | 2. 11-4.19.4 EXPOSED PIPES & SURFACES | | | -FOR THE BREAK ROOM SINK: | | | 1. 11-4.24.6 EXPOSED PIPES & SURFACES | | | 2. 11-4.24.7 FAUCETS | | | | | | B. ROOF DRAINAGE CALCULATIONS DO NOT INDICATE VERTICAL | | | CONTRIBUTIONS. SHOW 1/2 AREA OF ALL VERTICAL WALLS, | | | INCLUDING PARAPETS AS REQUIRED IN SECTION 1106.4. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|