Plan Review Notes
Plan Review Notes For Permit 06011055
Permit Number 06011055
Review Stop P
Sequence Number 3
Notes
Date Text
2007-03-10 08:05:09DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 FROM PREVIOUS REVIEWS:
  
 A. SHOW COMPLIANCE FOR THE FOLLOWING:
 -FOR THE URINAL:
 1. 11-4.18.2HEIGHT
 2. 11-4.18.3 CLEAR FLOOR SPACE
 3. 11-4.18.4 FLUSH CONTROLS
 -FOR THE LAVS:
 1. 11-4.19.2 CLEARANCE SHOWN AS 28" BUT 29" REQUIRED
 2. 11-4.19.4 EXPOSED PIPES & SURFACES
 -FOR THE BREAK ROOM SINK:
 1. 11-4.24.6 EXPOSED PIPES & SURFACES
 2. 11-4.24.7 FAUCETS
  
 B. ROOF DRAINAGE CALCULATIONS DO NOT INDICATE VERTICAL
 CONTRIBUTIONS. SHOW 1/2 AREA OF ALL VERTICAL WALLS,
 INCLUDING PARAPETS AS REQUIRED IN SECTION 1106.4.
  