Plan Review Notes For Permit 06011055
Permit Number 06011055
Review Stop E
Sequence Number 3
Notes
Date Text
2007-02-19 09:58:13*** UNSAT 3RD REVIEW***
  
 1) NOTE: PLEASE SEE THE DIFFERENCES IN THE FLORIDA
 ENERGY CALCULATIONS SUBMITTED AND THE PLANS.
 PLEASE SEE THE SQ FT SHOWN ON PLANS IS NOTED AT 6400
 AND THE CALCULATIONS INDICATE 5818.
 PLEASE SEE THE PLANS CLEARLY SHOW SEVERAL EXTERIOR
 LIGHTING FIXTURES; HOWEVER NONE ENTERED INTO THE ENERGY
 CALCULATIONS.
 PLEASE SEE SITE LIGHTING PLANS WHICH CONTAIN LIGHTING
 FIXTURES; HOWEVER NO INFORMATION WAS SHOWN FOR THESE.
 PLEASE SEE THE ENERGY CALCULATIONS INDICATE *1* FIXTURE
 AT 6300 VA/WATTS. IT IS BEING ASSUMED THIS IS ACTUALLY
 ALL OF THE FIXTURES ADDED, HOWEVER THIS DOES NOT
 CORRELATE WITH TABLE OR THE FIXTURES ON PLANS.
 (EXTERIOR ETC). PLEASE SEE TAHT ALL FIXTURES SHOULD BE
 LISTED AS THEY ARE ON PLANS.
 PLEASE SEE MAXIMUM TIMES WHICH ARE TO BE LISTED FOR THE
 OC SENSOR TYPE DEVICES.
 PLEASE VERIFY TYPE OF DEVICE BEING QUOTED FOR USE IN
 BATHROOMS, AS THERE ARE DEVICES WHICH WILL NOT PROVIDE
 COVERAGE FOR STALLS.THIS DEVICE WAS RESEARCHED ON THE
 COMPANY?S WEBSITE AND THIS DEVICE IS NOTED FOR MOTION
 ONLY. THERE ARE DEVICES WHICH COVER SOUND/MOTION/HEAT
 ETC. (PLEASE VERIFY AS LIGHTING BEING DEACTIVATED WHILE
 A RESTROOM IS OCCUPIED IS A SAFETY ISSUE).
  
 13-415.1.ABC.1.1, .1.2, AND .1.3
 13-415.1AB.1, 13-415.2
  
 2) NOTE: PLEASE SEE NOTES ON ELECTRICAL PLANS STATE THE
 * LATEST ADOPTED EDITIONS OF THE NATIONAL ELECTRICAL
 CODE*. PLEASE KNOW SINCE THE STATE HAS ALREADY ADOPTED
 THE LATEST EDITION WHICH IS THE 2005 NFPA-70, THIS NOTE
 SHOULD STATE THE CODE IN WHICH THESE PLANS ARE UNDER.
 THE CODE LISTED ON THE ARCHITECTURAL SHEET WAS NOTED ON
 A-1; HOWEVER THIS STATEMENT ON THE ELECTRICAL SHEETS IS
 NOT ACCURATE. THIS WOULD HAVE BEEN REDLINED; HOWEVER
 PLANS ARE COMING BACK FOR NOTE #1.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE/REVIEWER.IF THE NOTES TYPED
 ARE NOT CLEAR OR UNDERSTOOD IN ANY WAY, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]