| 2007-02-19 09:58:13 | *** UNSAT 3RD REVIEW*** |
| | |
| | 1) NOTE: PLEASE SEE THE DIFFERENCES IN THE FLORIDA |
| | ENERGY CALCULATIONS SUBMITTED AND THE PLANS. |
| | PLEASE SEE THE SQ FT SHOWN ON PLANS IS NOTED AT 6400 |
| | AND THE CALCULATIONS INDICATE 5818. |
| | PLEASE SEE THE PLANS CLEARLY SHOW SEVERAL EXTERIOR |
| | LIGHTING FIXTURES; HOWEVER NONE ENTERED INTO THE ENERGY |
| | CALCULATIONS. |
| | PLEASE SEE SITE LIGHTING PLANS WHICH CONTAIN LIGHTING |
| | FIXTURES; HOWEVER NO INFORMATION WAS SHOWN FOR THESE. |
| | PLEASE SEE THE ENERGY CALCULATIONS INDICATE *1* FIXTURE |
| | AT 6300 VA/WATTS. IT IS BEING ASSUMED THIS IS ACTUALLY |
| | ALL OF THE FIXTURES ADDED, HOWEVER THIS DOES NOT |
| | CORRELATE WITH TABLE OR THE FIXTURES ON PLANS. |
| | (EXTERIOR ETC). PLEASE SEE TAHT ALL FIXTURES SHOULD BE |
| | LISTED AS THEY ARE ON PLANS. |
| | PLEASE SEE MAXIMUM TIMES WHICH ARE TO BE LISTED FOR THE |
| | OC SENSOR TYPE DEVICES. |
| | PLEASE VERIFY TYPE OF DEVICE BEING QUOTED FOR USE IN |
| | BATHROOMS, AS THERE ARE DEVICES WHICH WILL NOT PROVIDE |
| | COVERAGE FOR STALLS.THIS DEVICE WAS RESEARCHED ON THE |
| | COMPANY?S WEBSITE AND THIS DEVICE IS NOTED FOR MOTION |
| | ONLY. THERE ARE DEVICES WHICH COVER SOUND/MOTION/HEAT |
| | ETC. (PLEASE VERIFY AS LIGHTING BEING DEACTIVATED WHILE |
| | A RESTROOM IS OCCUPIED IS A SAFETY ISSUE). |
| | |
| | 13-415.1.ABC.1.1, .1.2, AND .1.3 |
| | 13-415.1AB.1, 13-415.2 |
| | |
| | 2) NOTE: PLEASE SEE NOTES ON ELECTRICAL PLANS STATE THE |
| | * LATEST ADOPTED EDITIONS OF THE NATIONAL ELECTRICAL |
| | CODE*. PLEASE KNOW SINCE THE STATE HAS ALREADY ADOPTED |
| | THE LATEST EDITION WHICH IS THE 2005 NFPA-70, THIS NOTE |
| | SHOULD STATE THE CODE IN WHICH THESE PLANS ARE UNDER. |
| | THE CODE LISTED ON THE ARCHITECTURAL SHEET WAS NOTED ON |
| | A-1; HOWEVER THIS STATEMENT ON THE ELECTRICAL SHEETS IS |
| | NOT ACCURATE. THIS WOULD HAVE BEEN REDLINED; HOWEVER |
| | PLANS ARE COMING BACK FOR NOTE #1. |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE/REVIEWER.IF THE NOTES TYPED |
| | ARE NOT CLEAR OR UNDERSTOOD IN ANY WAY, PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-02-18 16:39:39 | IN ELEC FOR REVIEW |