Plan Review Notes
Plan Review Notes For Permit 06011055
Permit Number 06011055
Review Stop P
Sequence Number 2
Notes
Date Text
2006-08-06 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 UNSAT
  
 1) SEE OTHER PLAN REVIEW COMMENTS, THAT
 MAY EFFECT PLUMBING PLAN REVIEW.
  
 PREVIOUS NOTE #4 NOT ADDRESSED.
 SHT A-5 TURNING SPACE NOT SHOWN IN
 TOILET ROOM.
 SHT P1.01 TURNING SPACE SHOULD NOT BE
 SHOWN IN MEN, AND WOMENS STALLS.
  
 4) TOILET ROOMS
 11-4.22.3 CLEAR FLOOR SPACE.
 THE ACCESSIBLE FIXTURES AND CONTROLS
 REQUIRED IN SECTIONS 11-4.22.4,
 11-4.22.5, 11-4.22.6 AND 11-4.22.7 SHALL
 BE ON AN ACCESSIBLE ROUTE. AN
 UNOBSTRUCTED TURNING SPACE COMPLYING
 WITH SECTION 11-4.2.3 SHALL BE PROVIDED
 WITHIN AN ACCESSIBLE TOILET ROOM. THE
 CLEAR FLOOR SPACE AT FIXTURES AND
 CONTROLS, THE ACCESSIBLE ROUTE, AND THE
 TURNING SPACE MAY OVERLAP.
  
 NEW COMMENT SHT A6,A8 ROOF DRAINAGE.
  
 SECTION 1101
 GENERAL
 1101.1 SCOPE.
 THE PROVISIONS OF THIS CHAPTER SHALL
 GOVERN THE MATERIALS, DESIGN,
 CONSTRUCTION AND INSTALLATION OF STORM
 DRAINAGE.
 1101.2 WHERE REQUIRED.
 ALL ROOFS, PAVED AREAS, YARDS, COURTS
 AND COURTYARDS SHALL DRAIN INTO A
 SEPARATE STORM SEWER SYSTEM, OR A
 COMBINED SEWER SYSTEM, OR TO AN APPROVED
 PLACE OF DISPOSAL.
  
 1101.7 ROOF DESIGN.
 ROOFS SHALL BE DESIGNED FOR THE MAXIMUM
 POSSIBLE DEPTH OF WATER THAT WILL POND
 THEREON AS DETERMINED BY THE RELATIVE
 LEVELS OF ROOF DECK AND OVERFLOW WEIRS,
 SCUPPERS, EDGES OR SERVICEABLE DRAINS IN
 COMBINATION WITH THE DEFLECTED
 STRUCTURAL ELEMENTS. IN DETERMINING THE
 MAXIMUM POSSIBLE DEPTH OF WATER, ALL
 PRIMARY ROOF DRAINAGE MEANS SHALL BE
 ASSUMED TO BE BLOCKED.
  
 SECTION 1106
 SIZE OF CONDUCTORS, LEADERS
 AND STORM DRAINS
 1106.1 GENERAL.
 THE SIZE OF THE VERTICAL CONDUCTORS AND
 LEADERS, BUILDING STORM DRAINS, BUILDING
 STORM SEWERS, AND ANY HORIZONTAL
 BRANCHES OF SUCH DRAINS OR SEWERS SHALL
 BE BASED ON THE 100-YEAR HOURLY RAINFALL
 RATE INDICATED IN FIGURE 1106.1 OR ON
 OTHER RAINFALL RATES DETERMINED FROM
 APPROVED LOCAL WEATHER DATA.
  
 END OF COMMENTS, QUESTIONS 561-805-6692
  
  
  