Plan Review Notes
Plan Review Notes For Permit 06011055
Permit Number 06011055
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2006-08-23 00:00:00***DENIED***
  
 PLEASE NOTE THAT THE FIRST REVIEW WAS
 PASSED, HOWEVER COMMENTS WERE PROVIDED
 THAT HAVE NOT BEEN ACKNOWLEDGED. PLEASE
 SEE THE FOLLOWING WITH SOME ADDITIONS.
  
 1) DUCT SMOKE DETECTORS ARE REQUIRED TO
 BE EQUIPED WITH OCCUPANT NOTIFICATION
 DEVICES NEAR UNIT.
  
 2) RAMPS SHALL HAVE HANDRAILS ON BOTH
 SIDES.
  
 3) IF BUILDING IS SET BACK AT DISTANCE
 GREATER THAN 150' FROM MAIN ROAD, FIRE
 LANES WILL BE REQUIRED.
  
 4) AN ADDRESS IS REQUIRED ON BUILDING TO
 BE AT LEAST 6" IN HEIGHT AND CONTRASTING
 TO THE BACKGROUND. PLEASE ILLUSTRATE ON
 ELEVATIONS.
  
 5) PLEASE INDICATE THE LOCATIONS OF 2A
 10B,C RATED FIRE EXTINGUISHERS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722