Plan Review Notes
Plan Review Notes For Permit 06011055
Permit Number 06011055
Review Stop E
Sequence Number 2
Notes
Date Text
2006-08-02 00:00:00******* UNSAT 2ND REVIEW ********
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND SOME NEW NOTES DUE TO CHANGES
 IN PLANS.
  
 1) NOTE: PLEASE BE SURE PLANS REFLECT
 THE FOLLOWING CODES AT A MINIMUM.
 REPSONSE FROM ARCH MENTIONS THIS WAS
 DONE, HOWEVER COULD NOT LOCATE THIS ON
 PLANS.
 2002 NFPA-70 , 2002 NFPA-72, 2003
 NFPA-101
  
 2) NOTE: PLEASE SEE FBC CHAPTER 13.
 PLEASE PROVIDE THE AUTOMATIC CONTROLS,
 CONTROLS FOR SEPARATE SPACES ETC. PLEASE
 PROVIDE OVER RIDES AND LOCATIONS AS
 REQUIRED.
 PLEASE PROVIDE CALCULATIONS WHICH
 INDICAT ETH LIGHTING LEVELS PERMITTED
 AND LEVELS IN DESIGN.
 PLEASE SEE OTHER ENERGY CALCULATIONS
 SUBMITTED ARE INDICATING ALL MANUAL
 CONTROLS, AND DOES NOT INDICATE LIGHTING
 DESIGN WATTAGE, AND ALLOWANCE WATTAGE.
 PLEASE SEE 13415.1.ABC.1.1,.1.2,.1.3
 13415.1.AB.1,13415.2.ABC.1, TABLES
 415.2.C.1,415.2.B.1, ETC.
  
 3) NOTE: PLEASE SEE ENERGY CALCULATIONS
 AS THESE CONTAIN A RAISED SEAL OVER A
 PHOTO-COPY OF THE ENGINEER'S SIGNATURE
 WHICH IS REQUIRED TO BE ORIGINAL
 SIGNATURE.
 FAC 61G15-23.002, FS 471.025
  
 3) NOTE: PLEASE SEE PREVIOUS NOTES
 REQUESTED THE SEC'S CONDUCTORS TO BE
 SHOWN FROM THE METER TO THE FIRST MEANS
 OF DISCONNECT, HOWEVER PLEASE SEE NOW AN
 "EQUIPMENT GROUNDING CONDUCTOR" IS NOW
 BEING SHOWN BEFORE THE FIRST MEANS OF
 DISCONNECT.
 250.6,250.24B
  
 4) NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO DESIGN PROFESSIONALS.
 THIS IS ONLY A NOTICE WHICH IS GIVEN AT
 THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  