| 2006-08-02 00:00:00 | ******* UNSAT 2ND REVIEW ******** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW AND SOME NEW NOTES DUE TO CHANGES |
| | IN PLANS. |
| | |
| | 1) NOTE: PLEASE BE SURE PLANS REFLECT |
| | THE FOLLOWING CODES AT A MINIMUM. |
| | REPSONSE FROM ARCH MENTIONS THIS WAS |
| | DONE, HOWEVER COULD NOT LOCATE THIS ON |
| | PLANS. |
| | 2002 NFPA-70 , 2002 NFPA-72, 2003 |
| | NFPA-101 |
| | |
| | 2) NOTE: PLEASE SEE FBC CHAPTER 13. |
| | PLEASE PROVIDE THE AUTOMATIC CONTROLS, |
| | CONTROLS FOR SEPARATE SPACES ETC. PLEASE |
| | PROVIDE OVER RIDES AND LOCATIONS AS |
| | REQUIRED. |
| | PLEASE PROVIDE CALCULATIONS WHICH |
| | INDICAT ETH LIGHTING LEVELS PERMITTED |
| | AND LEVELS IN DESIGN. |
| | PLEASE SEE OTHER ENERGY CALCULATIONS |
| | SUBMITTED ARE INDICATING ALL MANUAL |
| | CONTROLS, AND DOES NOT INDICATE LIGHTING |
| | DESIGN WATTAGE, AND ALLOWANCE WATTAGE. |
| | PLEASE SEE 13415.1.ABC.1.1,.1.2,.1.3 |
| | 13415.1.AB.1,13415.2.ABC.1, TABLES |
| | 415.2.C.1,415.2.B.1, ETC. |
| | |
| | 3) NOTE: PLEASE SEE ENERGY CALCULATIONS |
| | AS THESE CONTAIN A RAISED SEAL OVER A |
| | PHOTO-COPY OF THE ENGINEER'S SIGNATURE |
| | WHICH IS REQUIRED TO BE ORIGINAL |
| | SIGNATURE. |
| | FAC 61G15-23.002, FS 471.025 |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS NOTES |
| | REQUESTED THE SEC'S CONDUCTORS TO BE |
| | SHOWN FROM THE METER TO THE FIRST MEANS |
| | OF DISCONNECT, HOWEVER PLEASE SEE NOW AN |
| | "EQUIPMENT GROUNDING CONDUCTOR" IS NOW |
| | BEING SHOWN BEFORE THE FIRST MEANS OF |
| | DISCONNECT. |
| | 250.6,250.24B |
| | |
| | 4) NOTE: PLEASE SEE FS 553.80(2)(B) WITH |
| | RESPECT TO DESIGN PROFESSIONALS. |
| | THIS IS ONLY A NOTICE WHICH IS GIVEN AT |
| | THIS TIME. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |