Plan Review Notes
Plan Review Notes For Permit 06011055
Permit Number 06011055
Review Stop B
Sequence Number 2
Notes
Date Text
2006-08-07 00:00:00BUILDING PLAN REVIEW
 PERMIT: 0611055
 ADD: 2924 AUSTRALIAN AVE.
 CONT: WOLFF & CO
 TEL: (561)968-0484 EXT 0
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUM- BER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICA TION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3)PROVISO: 109.3.10* IMPACT OF
 CONSTRUCTION. ALL CONSTRUCTION ACTIVITY
 REGULATED BY THIS CODE SHALL BE
 PERMORMED IN A MANNER SO AS NOT TO
 ADVERSLY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORICSURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGNCOMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES.ACCORDINGLY,
 DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENET, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 4) PROVISO: 109.3.10.1 HURICANE
 PROTECTION. IT SHALL BE UNLAWFUL FOR ANY
 PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENET AND DEBRIS TO
 REMAIN LOOSE OR OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A
 HURRICANE WATCH HAS BEEN ISSUED UNTIL
 THE HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM
 HIGHWINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 5) COMPLIED.
  
 6) 2ND REQUEST,
 W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 7) 2ND REQUEST,DEPENDING ON THE PRODUCT
 APPROVALS THE CONTRACTOR SUBMITTED
 OR IF OTHER PRODUCTS WILL BE SUBSTITUTED
 FROM THE ORIGINAL SUBMITTAL.
 1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 8) 2ND REQUEST, PRODUCT APPROVALS
 SUBMITTED WITH PERMIT APPLICATION AFTER
 OCTOBER 1, 2003 ARE REQUIRED TO COMPLY
 WITH THE FLORIDA PRODUCT APPROVAL
 SYSTEM. FOR INFORMATION PLEASE SEE THE
 STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 9) 2ND REQUEST, AGAIN DEPENDING ON THE
 CONTRACTORS NEXT SUBMITTAL THESE ARE THE
  
 REPORTS REQUIRED BY RULE 9B-72WITH
 FLORIDA COVER SHEET.
 A) FIXED GLASS
 B) STOREFRONT/ MULLIONS
 C) GLAZED DOORS
 D) EXT HOLLOW METAL DOORS
 E) OVERHEAD DOORS
 F)TRUSS ANCHORS
 G)ROOF ASSEMBLIES
 H) STORM SHUTTERS
  
 10) 2ND REQUEST,
 FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 11A) COMPLIED.
  
 11B) CONCRETE, PROVIDE THE EDITION OF
 ACI 318 LISTED IN CHAPTER 35 2004 FBC.
  
 11C) COMPLIED.
  
 11D) 2ND REQUEST, THE SAME NOTE
 REGAURDING HIGH RIB LATH NAILING INTO
 FRAMING: ASTM C-1063 7.10.2.3.
 EXPANDED 3/8" RIB LATH AND SHEET
 EXPANDED METAL LATH SHALL BE ATTACHED TO HORIZONTAL AND
 VERTICAL WOOD SUPPORTS
 WITH NAILS OR STAPLES TO PROVIDE AT
 LEAST 1 3/4" PENETRATION INTO HORIZONTAL
 WOOD SUPPORTS AND 3/4" PENETRATION INTO
 VERTICAL WOOD SUPPORTS.
  
 11E) COMPLIED.
  
 12A & B) BOTH DEAL WITH THE ICENENE
 INSULATION. SHEET A-10 DETAIL# 2
 INDICATES A EXTERIOR BLOCK WALL WITH A
 R=4.2 FOIL INSULATION TO THE CEILING
 HEIGTH. THIS IS TO BE A COMPLETE
 INSULATION PACKAGE TO THE UNDERSIDE OF
 THE ROOF, MISSING INSULATION ABOVE THE
 CEILING ON THE BLOCK WALL.
  
 THE SECOND ISSUE WITH THE ICENENE
 INSULATION IS THE REQUIREMENTS SET UP BY
 THE PALMBEACHCOUNTY BUILDING CODE
 ADVISORY BOARD FOR ALTERNATE MATERIALS
 AND METHODS. SEE ATTACHMENT. SEE
 REQUIREMENT 2 AND 3. REQUIREMENT# 2 WAS
 DISCUSSED IN THE PARAGRAPH ABOVE.
  
 THE THIRD ISSUE WILL BE TO GET A
 AFFIDAVIT FROM THE ROOFING MATERIAL /
 SYSTEMS MANUFACTURER, WHO SHALL PROVIDE
 AN AFFIDAVIT CERTIFYING USE OF THEIR
 PRODUCT OVER AN UNVENTED ATTIC SYSTEM. (NOTIRIZED).
  
 13) 2ND REQUEST, PLANS INDICATE VARIOUS
 TYPE OF TRUSS ANCHORS. THE PLANS
 INDICATE THE MANUFACTURER TO BE SIMPSON,
 BUT THE MODEL NUMBERS ARE USP. THE
 RESPONCE LETTER STATES USP. PLEASE
 CHANGE THE PLANS TO THE CORRECT
 MANUFACTURER.
  
 14) COMPLIED.
  
 15) 2ND REQUEST,
 BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  