Date Text
2006-04-01 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 UNSAT
  
 1) SEE OTHER PLAN REVIEW COMMENTS, THAT
 MAY EFFECT PLUMBING PLAN REVIEW.
  
 2) SHT A5 PRIVATE REST ROOM.
  
 (11) TOILET FACILITIES. IF TOILET ROOMS
 ARE PROVIDED, THEN EACH PUBLIC AND
 COMMON USE TOILET ROOM SHALL COMPLY WITH
 SECTION 11-4.22. OTHER TOILET ROOMS
 PROVIDED FOR THE USE OF OCCUPANTS OF
 SPECIFIC SPACES (I.E., A PRIVATE TOILET
 ROOM FOR THE OCCUPANT OF A PRIVATE
 OFFICE) SHALL BE ADAPTABLE. IF BATHING
 ROOMS ARE PROVIDED, THEN EACH PUBLIC AND
 COMMON USE BATHROOM SHALL COMPLY WITH
 SECTION 11-4.23. ACCESSIBLE TOILET ROOMS
 AND BATHING FACILITIES SHALL BE ON AN
 ACCESSIBLE ROUTE.
  
 3)SHT A5 SEC 11-4.17 TOILET STALLS,
 REMOVE TURNING CIRCLE, SHOW CLEAR FLOOR
 SPACE FOR EACH FIXTURE.
 SIZE AND ARRANGEMENT.
 THE SIZE AND ARRANGEMENT OF THE STANDARD
 TOILET STALL SHALL COMPLY WITH FIGURE
 11-30(A), STANDARD STALL. STANDARD
 TOILET STALLS WITH A MINIMUM DEPTH OF 56
 INCHES (1420 MM) [SEE FIGURE 11-30(A)]
 SHALL HAVE WALL-MOUNTED WATER CLOSETS.
 IF THE DEPTH OF A STANDARD TOILET STALL
 IS INCREASED AT LEAST 3 INCHES (76 MM),
 THEN A FLOOR-MOUNTED WATER CLOSET MAY BE
 USED. ARRANGEMENTS SHOWN FOR STANDARD
 TOILET STALLS MAY BE REVERSED TO ALLOW
 EITHER A LEFT-OR RIGHT-HAND APPROACH.
 ADDITIONAL STALLS SHALL BE PROVIDED IN
 CONFORMANCE WITH SECTION 11-4.22.4.
  
 4) TOILET ROOMS
 11-4.22.3 CLEAR FLOOR SPACE.
 THE ACCESSIBLE FIXTURES AND CONTROLS
 REQUIRED IN SECTIONS 11-4.22.4,
 11-4.22.5, 11-4.22.6 AND 11-4.22.7 SHALL
 BE ON AN ACCESSIBLE ROUTE. AN
 UNOBSTRUCTED TURNING SPACE COMPLYING
 WITH SECTION 11-4.2.3 SHALL BE PROVIDED
 WITHIN AN ACCESSIBLE TOILET ROOM. THE
 CLEAR FLOOR SPACE AT FIXTURES AND
 CONTROLS, THE ACCESSIBLE ROUTE, AND THE
 TURNING SPACE MAY OVERLAP.
  
 5) SHT P1.01 WATER HEATER
 607.3 THERMAL EXPANSION CONTROL.
 A MEANS OF CONTROLLING INCREASED
 PRESSURE CAUSED BY THERMAL EXPANSION
 SHALL BE PROVIDED WHERE REQUIRED IN
 ACCORDANCE WITH SECTIONS 607.3.1 AND
 607.3.2.
  
 6)SHT A5 BREAK ROOM SINK.
 11-4.24 SINKS.
 11-4.24.1 GENERAL.
 SINKS REQUIRED TO BE ACCESSIBLE BY
 SECTION 11-4.1 SHALL COMPLY WITH SECTION
 11-4.24.
 11-4.24.2 HEIGHT.
 SINKS SHALL BE MOUNTED WITH THE COUNTER
 OR RIM NO HIGHER THAN 34 INCHES (865 MM)
 ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE.
 KNEE CLEARANCE THAT IS AT LEAST 27
 INCHES (685 MM) HIGH, 30 INCHES (760 MM)
 WIDE, AND 19 INCHES (485 MM) DEEP SHALL
 BE PROVIDED UNDERNEATH SINKS.
 11-4.24.4 DEPTH.
 EACH SINK SHALL BE A MAXIMUM OF 6?
 INCHES (165 MM) DEEP.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES
 BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE
 PROVIDED IN FRONT OF A SINK TO ALLOW
 FORWARD APPROACH. THE CLEAR FLOOR SPACE
 SHALL BE ON AN ACCESSIBLE ROUTE AND
 SHALL EXTEND A MAXIMUM OF 19 INCHES (485
 MM) UNDERNEATH THE SINK (SEE FIGURE
 11-32).
 11-4.24.6 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED UNDER
 SINKS SHALL BE INSULATED OR OTHERWISE
 CONFIGURED SO AS TO PROTECT AGAINST
 CONTACT. THERE SHALL BE NO SHARP OR
 ABRASIVE SURFACES UNDER SINKS.
 11-4.24.7 FAUCETS.
 FAUCETS SHALL COMPLY WITH SECTION
 11-4.27.4. LEVER-OPERATED, PUSH-TYPE,
 TOUCH-TYPE, OR ELECTRONICALLY CONTROLLED
 MECHANISMS ARE ACCEPTABLE DESIGNS.
  
 END OF COMMENTS, QUESTIONS 561-805-6692
  
  
  
  
  