Plan Review Notes
Plan Review Notes For Permit 06011055
Permit Number 06011055
Review Stop E
Sequence Number 1
Notes
Date Text
2006-03-02 00:00:00********UNSAT ***********
  
 1)NOTE: PLEASEBE SURE ALL CURRENT
 CODES FOR THE FOLLOWING ARE REFERENCED
 ON ELECTRICAL PLANS.
 2002 NFPA-70, 2003 NFPA-101, 2002
 NFPA-72.
 PLEASE SEE SHEETS A-1 WHICH REFLECTS THE
 2001 FBC AND OTHER SHEETS REFLECT 2004
 FBC.
 PLEASE KNOW, THE STATE OF FLORIDA
 ADOPTED THE 2004 FBC ON OCT 1ST, 2005
  
 2)NOTE: PLEASE BE SURE ALL SHEETS ARE
 SIGNED DATED AND SEALED AS REQUIRED PER
 FS 471.025
 ** PLEASE SEE C-3, (NOT SIGNED) THIS IS
 NOTE ONLY, AS NOT PART OF THE ELECTRICAL
 SHEETS.
  
 3)NOTE: PLEASE SEE THE ELECTRICAL NOTES
 ON A-1 ARE PERTAINING TO WHAT APPEARS TO
 BE A RESIDENTIAL HOUSE?
 PLEASE CORRELATE WITH ELECTRICAL NOTES
 BY ENGINEER OR REMOVE.
  
 4)NOTE: PLEASE SEE 210.8B3 FOR ALL
 15/20A 125V CIRCUITS IN KITCHEN IN OTHER
 THAN DWELLING UNITS WHICH REQUIRED GFI
 PROTECTION.
  
 5)NOTE: PLEASE SEE FBC CHAPTER 13, FOR
 THE NEW REWUIREMENTS FOR COMMERCIAL
 BLGDS.
 PLEASE SEE A WORST CASE CALCUALTION TO
 BE SHOWN FOR VOTLAGE DROP TO MEET THE
 MIN AS SET FORTH IN 13-413.1ABC.1
 PLEASE SEE 13-415.1.ABC.1 & .2 FOR
 INTERIOR LIGHTING SHUTOFF, SPACE
 LIGHTING CONTROLS REQUIRED.PLEASE
 PROVIDE SCHEDULING.
 PLEASE SEE 13.415.1.ABC.1.4 FOR EXTERIOR
 LTS, AND TYPE OF TIME CLOCK REQUIRED .
 PLEASE SEE 13-415.1.ABC.3 TANDEM WIRING.
 PLEASE SEE 13-415.1.ABC.1 FOR
 CALCULATIONS.
  
 6)NOTE: PLEASE CLARIFY "UTILITY RM " AS
 SHOWN, PLEASE IDENTIFY AS "ELECTRICAL
 RM", NO STORAGE OF EASILY IGNITIBLE
 MATERIALS ARE PERMITTED.
 110.26,408.7,240.24
  
 7)NOTE: PLEASE SEE GROUNDING ELECTRODE
 SYSTEM TO GO TO "FOOTER STEEL", PLANS
 INDICATE THE "SLAB STEEL". PLEASE SEE
 250.50,250.52 ETC.
 THERE IS SLAB STEEL AND THE CONNECTION
 IS REQUIRED WITHIN THE BOTTOM OF THE
 FOOTER.
  
 8)NOTE: PLEASE INDICATE THE CONDUCTORS
 FROM THE WIREWAY TO THE MAINS.
 215.5
  
 ** PLEASE SEE ANY OTHER POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
  
 ** PLEASE COMPLETETLY REMOVED ANY
 OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT TEH ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-03-01 00:00:00IN ELEC FOR REVIEW