| 2006-03-02 00:00:00 | ********UNSAT *********** |
| | |
| | 1)NOTE: PLEASEBE SURE ALL CURRENT |
| | CODES FOR THE FOLLOWING ARE REFERENCED |
| | ON ELECTRICAL PLANS. |
| | 2002 NFPA-70, 2003 NFPA-101, 2002 |
| | NFPA-72. |
| | PLEASE SEE SHEETS A-1 WHICH REFLECTS THE |
| | 2001 FBC AND OTHER SHEETS REFLECT 2004 |
| | FBC. |
| | PLEASE KNOW, THE STATE OF FLORIDA |
| | ADOPTED THE 2004 FBC ON OCT 1ST, 2005 |
| | |
| | 2)NOTE: PLEASE BE SURE ALL SHEETS ARE |
| | SIGNED DATED AND SEALED AS REQUIRED PER |
| | FS 471.025 |
| | ** PLEASE SEE C-3, (NOT SIGNED) THIS IS |
| | NOTE ONLY, AS NOT PART OF THE ELECTRICAL |
| | SHEETS. |
| | |
| | 3)NOTE: PLEASE SEE THE ELECTRICAL NOTES |
| | ON A-1 ARE PERTAINING TO WHAT APPEARS TO |
| | BE A RESIDENTIAL HOUSE? |
| | PLEASE CORRELATE WITH ELECTRICAL NOTES |
| | BY ENGINEER OR REMOVE. |
| | |
| | 4)NOTE: PLEASE SEE 210.8B3 FOR ALL |
| | 15/20A 125V CIRCUITS IN KITCHEN IN OTHER |
| | THAN DWELLING UNITS WHICH REQUIRED GFI |
| | PROTECTION. |
| | |
| | 5)NOTE: PLEASE SEE FBC CHAPTER 13, FOR |
| | THE NEW REWUIREMENTS FOR COMMERCIAL |
| | BLGDS. |
| | PLEASE SEE A WORST CASE CALCUALTION TO |
| | BE SHOWN FOR VOTLAGE DROP TO MEET THE |
| | MIN AS SET FORTH IN 13-413.1ABC.1 |
| | PLEASE SEE 13-415.1.ABC.1 & .2 FOR |
| | INTERIOR LIGHTING SHUTOFF, SPACE |
| | LIGHTING CONTROLS REQUIRED.PLEASE |
| | PROVIDE SCHEDULING. |
| | PLEASE SEE 13.415.1.ABC.1.4 FOR EXTERIOR |
| | LTS, AND TYPE OF TIME CLOCK REQUIRED . |
| | PLEASE SEE 13-415.1.ABC.3 TANDEM WIRING. |
| | PLEASE SEE 13-415.1.ABC.1 FOR |
| | CALCULATIONS. |
| | |
| | 6)NOTE: PLEASE CLARIFY "UTILITY RM " AS |
| | SHOWN, PLEASE IDENTIFY AS "ELECTRICAL |
| | RM", NO STORAGE OF EASILY IGNITIBLE |
| | MATERIALS ARE PERMITTED. |
| | 110.26,408.7,240.24 |
| | |
| | 7)NOTE: PLEASE SEE GROUNDING ELECTRODE |
| | SYSTEM TO GO TO "FOOTER STEEL", PLANS |
| | INDICATE THE "SLAB STEEL". PLEASE SEE |
| | 250.50,250.52 ETC. |
| | THERE IS SLAB STEEL AND THE CONNECTION |
| | IS REQUIRED WITHIN THE BOTTOM OF THE |
| | FOOTER. |
| | |
| | 8)NOTE: PLEASE INDICATE THE CONDUCTORS |
| | FROM THE WIREWAY TO THE MAINS. |
| | 215.5 |
| | |
| | ** PLEASE SEE ANY OTHER POSSIBLE |
| | COMMENTS FROM OTHER TRADES WHICH MAY |
| | AFFECT ELECTRICAL PLANS. |
| | |
| | |
| | ** PLEASE COMPLETETLY REMOVED ANY |
| | OLD/VOIDED SHEETS FROM SETS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO TWO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT TEH ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |