Plan Review Notes
Plan Review Notes For Permit 06011055
Permit Number 06011055
Review Stop B
Sequence Number 1
Notes
Date Text
2006-04-24 00:00:00BUILDING PLAN REVIEW
 PERMIT: 0611055
 ADD: 2924 AUSTRALIAN AVE.
 CONT: WOLFF & CO
 TEL: (561)968-0484 EXT 0
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUM- BER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICA TION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSLY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORICSURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGNCOMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED
 SITES.ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENET, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 4) 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM
 HIGHWINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 5) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 F) NUMBER OF ROOMS
  
 G) SQ. FT. LIV SPACE/ FL
  
 H) SQ. FT. FOOTPRINT
  
 I) SQ. FT. UNDER ROOF (TOTAL)
  
 J) OCCUPANT LOAD
  
 K) FLOOD ZONE
  
 L) FLOOD ELEVATION
  
 6) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 7) 1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
 8) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 9) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) FIXED GLASS
 B) STOREFRONT/ MULLIONS
 C) GLAZED DOORS
 D) EXT HOLLOW METAL DOORS
 E) OVERHEAD DOORS
 F) TRUSS ANCHORS
 G) ROOF ASSEMBLIES
 H) STORM SHUTTERS
  
 10)1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE
 SOIL IS IN DOUBT, OR WHERE A LOAD
 BEARING VALUE SUPERIOR TO THAT SPECIFIED
 IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE
 NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH
 1802.6 .
  
 11) SHEET A-1
 11A) GENERAL NOTE# 1 CORRECT EDITION OF
 CODE, 2001 FBC
  
 11B) CONCRETE, EDITIONS OF ACI 318,
  
 11C) WOOD & PLASTICS( PLASTERS?)
 NOTE (3) HIGH RIB LATH TO BE NAILED AT
 6" O.C. SEE 2510.3 INSTALATION OF CEMENT
 PLASTER AND LATH, IT REFERS TO ASTM
 C-1063, 7.10.1.1. HI RIB LATH TO BE
 ATTACHED AT EACH RIB (4") O. C.
  
 11D) SAME NOTE INDICATES (CORRECT) HI-
 RIB LATH TO BE ATTACHED WOOD FRAMING
 WITH 1 1/2 ROOFING NAILS.
 ASTM C-1063 7.10.2.3.
 EXPANDED 3/8" RIB LATH AND SHEET
 EXPANDED METAL LATH SHALL BE ATTACHED TO
 HORIZONTAL AND VERTICAL WOOD SUPPORTS
 WITH NAILS OR STAPLES TO PROVIDE AT
 LEAST 1 3/4" PENETRATION INTO HORIZONTAL
 WOOD SUPPORTS AND 3/4" PENETRATION INTO
 VERTICAL WOOD SUPPORTS.
  
 11E) FINISHES: NOTE# 1 INDICATES USE OF
 P.B.C. CODE CORRECT TO USE OF FBC SEE
 CHAPTER 8 FOR INTERIOR FINISHES.
  
 12A) SHEET A10 DETAIL# 1 , PLANS DO NOT
 INDICATE COMPLIANCE WITH VENTILATION FOR
  
 ATTIC SPACE.DETAIL# 2 SAME PAGE
 INDICATES USE OF ICENENE BUT NOT ON
 DETAIL# 1 WHERE WILL ICENENE STOP?
 1203.2 ATTIC SPACES.
 ENCLOSED ATTICS AND ENCLOSED RAFTER
 SPACES FORMED WHERE CEILINGS ARE APPLIED
 DIRECTLY TO THE UNDERSIDE OF ROOF
 FRAMING MEMBERS SHALL HAVE CROSS
 VENTILATION FOR EACH SEPARATE SPACE BY
 VENTILATING OPENINGS PROTECTED AGAINST
 THE ENTRANCE OF RAIN. BLOCKING AND
 BRIDGING SHALL BE ARRANGED SO AS NOT TO
 INTERFERE WITH THE MOVEMENT OF AIR. A
 MINIMUM OF 1 INCH (25 MM) OF AIRSPACE
 SHALL BE PROVIDED BETWEEN THE INSULATION
 AND THE ROOF SHEATHING. THE NET FREE
 VENTILATING AREA SHALL NOT BE LESS THAN
 1 / 150 OF THE AREA OF THE SPACE
 VENTILATED, WITH 50 PERCENT OF THE
 REQUIRED VENTILATING AREA PROVIDED BY
 VENTILATORS LOCATED IN THE UPPER PORTION
 OF THE SPACE TO BE VENTILATED AT LEAST 3
 FEET (914 MM) ABOVE EAVE OR CORNICE
 VENTS WITH THE BALANCE OF THE REQUIRED
 VENTILATION PROVIDED BY EAVE OR CORNICE
 VENTS.
  
 12B) WITH USE OF ICENENE INSULATION AT
 THE TOP CHORD OF TRUSS THIS SPACE
 BECOMES ADJOINING SPACE REQUIRING
 VENTILATION OR TRANSFER GRILLES.
 1203.4.1.1 ADJOINING SPACES.
 WHERE ROOMS AND SPACES WITHOUT OPENINGS
 TO THE OUTDOORS ARE VENTILATED THROUGH
 AN ADJOINING ROOM, THE OPENING TO THE
 ADJOINING ROOM SHALL BE UNOBSTRUCTED AND
 SHALL HAVE AN AREA OF NOT LESS THAN 8
 PERCENT OF THE FLOOR AREA OF THE
 INTERIOR ROOM OR SPACE, BUT NOT LESS
 THAN 25 SQUARE FEET.
  
 13) SHEET A-6 TRUSS ANCHOR SCHEDULE LIST
 (2) SIMPSON STRAPS, NEITHER STRAP IS
 LISTED UNDER THE CURRENT SIMPSON CATOLOG
 BUT THE LISTED NUMBERS FL LISTING AND
 VALUES ARE IN THE CURRENT USP CATOLOG.
  
 14) SHEET A-7 KITCHEN SINK:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARENCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
 15) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026