| Date |
Text |
| 2006-06-01 00:00:00 | ************UNSAT 2ND REVIEW ******** |
| | |
| | ** PLEASE SEE COMMENTS FROM PREVIOUS |
| | REVIEW AND SOME NEW COMMENTS FROM THIS |
| | REVIEW . |
| | |
| | |
| | 1) NOTE: PLEASE SUBMIT TWO COMPLETE SETS |
| | OF PLANS. PLEASE REMOVE ANY OLD/VOIDED |
| | SHEETS OR SETS AND ONLY SUBMIT ONE COPY |
| | OF OLD/VOIDED SHEETS/SETS SEPARATELY IN |
| | PACKAGE FOR REFERENCE. |
| | |
| | 2) NOTE: PLEASE SEE SOME OF THE NEW |
| | PLANS SUBMITTED ARE SEALED "PHOTO-COPIES |
| | OF SIGNED PLANS AND SHALL BE RETAINED BY |
| | THIS OFFICE FOR SUBMITTIAL TO THE |
| | FLORIDA BOARD OF PROFESSIONAL ENGINEERS |
| | AS OTHER PROJECTS AND REVIEWS HAVE HAD |
| | THE SAME COMMENT AND PLANS ARE STILL |
| | BEING SUBMITTED WITH THE SAME SIMILAR |
| | COMMENTS. PLEASE SEE FS 471.025 WHICH |
| | REQUIRES PLANS TO CONTAIN A RAISED SEAL, |
| | AND AN ORIGINAL SIGNATURE AND DATE BY |
| | THE SAID ENGINEER. |
| | PLEASE SEE SOME OTHER PLANS WERE |
| | SUBMITTED AFTER ORIGINAL DATE WHICH NOW |
| | CONTAINS ORIGINAL SIGNATURE. |
| | |
| | 3) NOTE:PLEASE ALSO SEE NEW "S" |
| | SHEETS. PLEASE SEE FAC 61G15-23.001 |
| | WHICH IN FEB 04 THE FBPE'S RULED THE |
| | "WORDING" IN THE SEAL SHALL BE CHANGED |
| | TO "LICENSE" FROM "CERTIFICATE". AN |
| | EXTENSION WAS GIVEN TO THE DATE OF |
| | 12/31/05 IN WHICH THE OLD SEALS MAY BE |
| | USED. PLEASE KNOW, THE SEAL AS SUBMITTED |
| | FOR THE "S" SHEETS ARE NO LONGER |
| | ACCEPTABLE UNDER FAC/ FLORIDA STATUES. |
| | PELAS OBTAIN NEW SEAL AND REVISE SHEETS |
| | ACCORDINGLY. |
| | |
| | 4) NOTE: PLEASE SUBMIT THE SPECS AS |
| | REQUESTED FOR THE ATS. UNABLE TO VERIFY |
| | CODE COMPLIANCE FOR MANY ITEMS AS THE |
| | ATS MUST MEET, |
| | 230.70,230.76,230.79,225.31-225.39. |
| | PLEASE SEE THE ATS IS REQUIRED TO BE |
| | RATED AS "SERVICE ENTRANCE", ETC. |
| | ONLY THE SPECS FOR THE GENERATOR WERE |
| | LOCATED IN PLANS AND PAPERWORK |
| | SUBMITTED. |
| | PLEASE BE SURE TO CORRELATE WITH PLANS. |
| | |
| | |
| | **PLEASE SUBMIT THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |