| Plan Review Notes For Permit 06011041 |
| Permit Number |
06011041 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-03-16 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE PROVIDE MANUFACTURER SPEC | | | SHEETS FOR GENERATOR, FUEL TANK AND | | | ASSOCIATED EQUIPMENT. | | | | | | 2) APPROPRIATE PROTECTION DEVICES MAY BE | | | REQUIRED IF FUEL TANK AND EQUIPMENT ARE | | | SUBJECT TO MECHANICAL DAMAGE. | | | | | | 3) PLEASE INDICATE SIZE OF VENT PIPING | | | AND LOCATION OF EXHAUSTING IN REGARDS TO | | | BUILDING OPENINGS, PROPERTY LINES ETC. | | | | | | 4) WORK TO COMPLY WITH CURRENT | | | APPLICABLE BUILDING AND LIFE SAFETY | | | CODES IN ADDITION TO NFPA 110. NFPA 101 | | | AND NFPA 1, 2003 EDITIONS SHALL BE | | | REFERENCED. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLANS REVIEW (561) 805-6722 |
|