Plan Review Notes
Plan Review Notes For Permit 06011041
Permit Number 06011041
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-03-16 00:00:00******DENIED******
  
 1) PLEASE PROVIDE MANUFACTURER SPEC
 SHEETS FOR GENERATOR, FUEL TANK AND
 ASSOCIATED EQUIPMENT.
  
 2) APPROPRIATE PROTECTION DEVICES MAY BE
 REQUIRED IF FUEL TANK AND EQUIPMENT ARE
 SUBJECT TO MECHANICAL DAMAGE.
  
 3) PLEASE INDICATE SIZE OF VENT PIPING
 AND LOCATION OF EXHAUSTING IN REGARDS TO
 BUILDING OPENINGS, PROPERTY LINES ETC.
  
 4) WORK TO COMPLY WITH CURRENT
 APPLICABLE BUILDING AND LIFE SAFETY
 CODES IN ADDITION TO NFPA 110. NFPA 101
 AND NFPA 1, 2003 EDITIONS SHALL BE
 REFERENCED.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722