| Date |
Text |
| 2006-03-02 00:00:00 | ********* UNSAT ********* |
| | |
| | 1)NOTE: PLEASE SEE BLDG REVIEW COMMENTS |
| | AS DETAIL FOR SLAB SHALL BE SIGNED, |
| | DATED AND SEALED. FS 481.221, 471.023 |
| | |
| | 2)NOTE: PLEASE SEE CURRENT CODES NEED TO |
| | BE REFERENCED ON PLANS. PLEASE SEE THAT |
| | WE ARE CURRENLTY UNDER THE 2004 FBC, |
| | 2003 NFPA-101, 2002 NFPA-110, 2002 |
| | NFPA-70 |
| | |
| | 3)NOTE: PLEASE SEE BLDG REVIEW COMMENTS |
| | WITH RESPECT TO BFE. |
| | PLEASE SEE NFPA-110 7.2.3* |
| | PLEASE NOTE AND VERIFY THE LOCATION OF |
| | GENERATOR. |
| | |
| | 4)NOTE: PLEASE SUBMIT ALL MANUFACTURE |
| | SPECS/CUT SHEETS FOR GEN, ATS, SUB BASE |
| | FUEL TANK, WP HOUSING. |
| | THE ONLY SPEC SUBMITTED WAS FOR THE |
| | GENERATOR WHICH INDICATES AND INDOOR |
| | UNIT. ASSUBMITTED, GEN IS SHOWN AS |
| | 54KW/KVA, WHERE-AS THE PERMIT |
| | APPLICATION MENTIONS 60KW?? |
| | PLEASE CORRELATE. |
| | |
| | 5)NOTE: PLEASE SEE EXISTING MCB IS SHOWN |
| | ON ROOF??? |
| | PLEASE VERIFY AS THIS IS NOT READILY |
| | ACCESSIBLE AS REQUIRED PER 230.70,PLEASE |
| | SEE MAINS ARE NOT GROUPED PER 230.72, |
| | 225.34. |
| | |
| | 6)NOTE: PLEASE SEE VALUATION IS BASED ON |
| | COMPLETE SCOPE PF WORK WHICH IS TO |
| | INCLUDE ALL LABOR AND MATERIALS, EVEN OF |
| | ANY EQUIPMENT IS OWNER SUPPLIED. VALUE |
| | AS SHOWN IS WAY LOW AND MAY BE ADJUSTED |
| | BY THIS OFFICE IF AN APPROPRIATE VALUE |
| | IS NOT INCREASED. |
| | THIS IS TO BE INCREASED WHEN |
| | RESUBMITTING PLANS AFTER ALL REVIEWS ARE |
| | COMPLETED. |
| | |
| | 7)NOTE: PLEASE SUBMIT THE INTENDED LOADS |
| | FOR GENERATOR. GEN MUS BE SIZED FOR |
| | LOADS SERVED. |
| | 220, 215.5 |
| | |
| | ** PLEASE SEE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| 2006-03-01 00:00:00 | IN ELEC FOR REVIEW. |