Plan Review Notes
Plan Review Notes For Permit 06011022
Permit Number 06011022
Review Stop M
Sequence Number 1
Notes
Date Text
2006-01-31 00:00:00*** PROVISO ***
 1) 26X16 NEW FIRE DAMPER TO BE INSTALLED
 AT TENANT SEPARATION WALL.
 2) EACH OFFICE MUST HAVE A RETURN AIR
 GRILL TO COMPLY WITH 2004 FBC/M 601.4 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  