Date Text
2006-03-17 00:00:00******DENIED******
  
 1) AN ADDRESS IS REQUIRED ON BUILDING
 AND SHALL BE A MINIMUM OF 6" IN HEIGHT
 AND CONTRASTING TO THE BACKGROUND.
  
 2) ARE FIRE SPRINKLER AND FIRE ALARM
 SYSTEMS PLANNED FOR THE BUILDING? SHT
 A-1 INDICATES UNSPRINKLED.
  
 3) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED AND SHALL BE MOUNTED AT
 DISTANCES NOT TO EXCEED 75'.
  
 4) PLEASE INDICATE THE LOCATION AND
 BUILDING DISTANCE TO THE CLOSEST FIRE
 HYDRANT.
  
 5) PLEASE PROVIDE FLAME RETARDANT
 INFORMATION FOR THE PROPOSED AWNING.
  
 6) WILL BUILDING HAVE ABILITY TO MEET
 TENANT SEPARATION REQUIREMENTS FOR
 FUTURE BUILDOUTS?
  
 7) PLANS DON'T ILLUSTRATE THE LOCATIONS
 OF EXIT SIGNS AND EMERGENCY LIGHTING
 FACILITIES.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722