Plan Review Notes
Plan Review Notes For Permit 06011012
Permit Number 06011012
Review Stop E
Sequence Number 1
Notes
Date Text
2006-03-01 00:00:00******* UNSAT *********
  
 2433 METROCENTRE BLVD, BLDG "F"
 PLANS SUBMITTED FOR "PLAN REVIEW" ONLY
 AND HAVE NOT BEEN SUBMITTED FOR PERMIT.
  
 1)NOTE: PLEASE BE SURE PLANS REFLECT AND
 ARE DESIGNED WITH THE CURRENT CODES
 ADOPTED BY THE STATE OF FLORIDA.
 PLEASE KNOW WE ARE CURRENTLY UNDER THE
 2004 FBC.
 PLEASE SEE SOME AREAS OF PLANS WHICH
 REFLECT 2001 FBC.
 ** PLEASE BE SURE ELECTRICAL PLANS
 INDICATE THE 2002 NFPA-72, 2002 NFPA-72
 AND 2003 NFPA-101.
  
 2)NOTE: PLEASE SEE MISSING SIZE FOR
 GROUNDING ELECTRODE CONDUCTOR.
 250.66
 PLEASE SEE EQUIPMENT GROUNDING
 CONDUCTORS BEING SHOWN BEFORE THE FRIST
 MEANS OF DISCONNECT. 250.6.
 PLEASE SEE ABOVE AS EQUIPMENT GROUNDING
 CONDUCTORS ARE ONLY INSTALLED AFTER THE
 FIRST MEANS OF DISCONNECT.
  
  
 3)NOTE: PLEASE INDICATE TH CONDUCTORS
 FROM GUTTER TO METER, METER TO HOUSE
 MAIN.215.5, 310.16, 240.4
  
 4)NOTE: PLEASE SEE IT APPEARS THAT THE
 MAINS WILL BE FUSED DISCONNECTS,?
 HOWEVER PLEASE INDICATE THE MIN AIC
 RATINGS FOR FUSES AND TYPES. 110.9,215.5
  
 5)NOTE: PLEASE KNOW, MIN LENGTH OF
 GUTTER SHOULD BE NOTED AND SHOWN BY THE
 DESIGNER.366,215.5
  
 6)NOTE: PLEASE SEE MISSING CERIFICATEOF
 AUTHORIZATION NUMBER FOR STRUCTURAL
 ENGINEERING COMPANY. PLEASE ALSO SEE
 MISSING TITLE BLCOK FOR ENGINEER AS
 SHOWN ON S-6.
 PLEASE KNOW, THIS IS ONLY A NOTE FOR THE
 ELECTRICLA REVIEW. PLEASE BE AWARE OF
 BLDG REVIEW FOR NOTES AS THIS DOES NOT
 APPLY TO CHANE ENGINEERING.
  
 7)NOTE: PLEASE SEE FBC CHAPTER 13,
 13-413.1.ABC.1
 PLEASE ALSO SEE TYPE OF TC REQUIRED FOR
 EXTERIOR LTS, 13-415.1.ABC.1.4
  
 8)NOTE: PLEASE BE SURE TO INDICATE THE
 ADDRESS OF JOB ON TITLE BLOCKS PER FAC
 61G1-16.004
  
 9)NOTE: PLEASE A NOTE ON PLAN MENTIONS A
 "BUILDING CONTRACTOR" TO DO ELECTRICLA
 SCOPE PF WORK FOR IRRIGATION?
 PLEASE VERIFY THIS NOTE AS A BLDG CONT
 MAY NOT WORK IN THE SCOPE OF THE
 ELECTRICAL.
  
 10)NOTE: PLEASE CLARIFY NOT FOR "SITE
 LIGHTING". NONE , SHOWN ON PLANS, ANY
 SITE INCLUDED ON THIS PERMIT WHEN
 APPLIED FOR MUST BE SHOWN WIHT WIND LOAD
 CALCUALTIONS ETC. IF THESE ITEMS ARE NOT
 PART OF THIS PERMIT, PLEASE UNDER
 SEPARATE PERMIT.
  
 11)NOTE:PANEL SCHEDULE INDICATE COVERED
 PARKING LIGHTING? IS THIS A STRUCTURE
 UNDER FUTURE PERMIT?
  
 ** PLEASE KNOW, A RESPONSE LTR MAY HELP
 IN THR PLAN REVIEW AND PROCESSING.
  
  
 ** PLEASE REMOVE ANY OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETED SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-02-28 00:00:00IN ELEC FOR REVIEW.