| Date |
Text |
| 2006-03-01 00:00:00 | ******* UNSAT ********* |
| | |
| | 2433 METROCENTRE BLVD, BLDG "F" |
| | PLANS SUBMITTED FOR "PLAN REVIEW" ONLY |
| | AND HAVE NOT BEEN SUBMITTED FOR PERMIT. |
| | |
| | 1)NOTE: PLEASE BE SURE PLANS REFLECT AND |
| | ARE DESIGNED WITH THE CURRENT CODES |
| | ADOPTED BY THE STATE OF FLORIDA. |
| | PLEASE KNOW WE ARE CURRENTLY UNDER THE |
| | 2004 FBC. |
| | PLEASE SEE SOME AREAS OF PLANS WHICH |
| | REFLECT 2001 FBC. |
| | ** PLEASE BE SURE ELECTRICAL PLANS |
| | INDICATE THE 2002 NFPA-72, 2002 NFPA-72 |
| | AND 2003 NFPA-101. |
| | |
| | 2)NOTE: PLEASE SEE MISSING SIZE FOR |
| | GROUNDING ELECTRODE CONDUCTOR. |
| | 250.66 |
| | PLEASE SEE EQUIPMENT GROUNDING |
| | CONDUCTORS BEING SHOWN BEFORE THE FRIST |
| | MEANS OF DISCONNECT. 250.6. |
| | PLEASE SEE ABOVE AS EQUIPMENT GROUNDING |
| | CONDUCTORS ARE ONLY INSTALLED AFTER THE |
| | FIRST MEANS OF DISCONNECT. |
| | |
| | |
| | 3)NOTE: PLEASE INDICATE TH CONDUCTORS |
| | FROM GUTTER TO METER, METER TO HOUSE |
| | MAIN.215.5, 310.16, 240.4 |
| | |
| | 4)NOTE: PLEASE SEE IT APPEARS THAT THE |
| | MAINS WILL BE FUSED DISCONNECTS,? |
| | HOWEVER PLEASE INDICATE THE MIN AIC |
| | RATINGS FOR FUSES AND TYPES. 110.9,215.5 |
| | |
| | 5)NOTE: PLEASE KNOW, MIN LENGTH OF |
| | GUTTER SHOULD BE NOTED AND SHOWN BY THE |
| | DESIGNER.366,215.5 |
| | |
| | 6)NOTE: PLEASE SEE MISSING CERIFICATEOF |
| | AUTHORIZATION NUMBER FOR STRUCTURAL |
| | ENGINEERING COMPANY. PLEASE ALSO SEE |
| | MISSING TITLE BLCOK FOR ENGINEER AS |
| | SHOWN ON S-6. |
| | PLEASE KNOW, THIS IS ONLY A NOTE FOR THE |
| | ELECTRICLA REVIEW. PLEASE BE AWARE OF |
| | BLDG REVIEW FOR NOTES AS THIS DOES NOT |
| | APPLY TO CHANE ENGINEERING. |
| | |
| | 7)NOTE: PLEASE SEE FBC CHAPTER 13, |
| | 13-413.1.ABC.1 |
| | PLEASE ALSO SEE TYPE OF TC REQUIRED FOR |
| | EXTERIOR LTS, 13-415.1.ABC.1.4 |
| | |
| | 8)NOTE: PLEASE BE SURE TO INDICATE THE |
| | ADDRESS OF JOB ON TITLE BLOCKS PER FAC |
| | 61G1-16.004 |
| | |
| | 9)NOTE: PLEASE A NOTE ON PLAN MENTIONS A |
| | "BUILDING CONTRACTOR" TO DO ELECTRICLA |
| | SCOPE PF WORK FOR IRRIGATION? |
| | PLEASE VERIFY THIS NOTE AS A BLDG CONT |
| | MAY NOT WORK IN THE SCOPE OF THE |
| | ELECTRICAL. |
| | |
| | 10)NOTE: PLEASE CLARIFY NOT FOR "SITE |
| | LIGHTING". NONE , SHOWN ON PLANS, ANY |
| | SITE INCLUDED ON THIS PERMIT WHEN |
| | APPLIED FOR MUST BE SHOWN WIHT WIND LOAD |
| | CALCUALTIONS ETC. IF THESE ITEMS ARE NOT |
| | PART OF THIS PERMIT, PLEASE UNDER |
| | SEPARATE PERMIT. |
| | |
| | 11)NOTE:PANEL SCHEDULE INDICATE COVERED |
| | PARKING LIGHTING? IS THIS A STRUCTURE |
| | UNDER FUTURE PERMIT? |
| | |
| | ** PLEASE KNOW, A RESPONSE LTR MAY HELP |
| | IN THR PLAN REVIEW AND PROCESSING. |
| | |
| | |
| | ** PLEASE REMOVE ANY OLD/VOIDED SHEETS |
| | AND ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETED SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF OLD/VOIDED SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| 2006-02-28 00:00:00 | IN ELEC FOR REVIEW. |