| 2006-04-25 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 06011012 |
| | ADD: 2433 METROCENTRE BLVD BLDG# F |
| | CONT:PLAN REVIEW/ QUEST |
| | TEL: (561)691-9400 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE |
| | ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUM- BER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET |
| | OR SPECIFICA TION PAGE WHERE THE CHANGES |
| | CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 2) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 3) 109.3.10* IMPACT OF CONSTRUCTION. ALL |
| | CONSTRUCTION ACTIVITY REGULATED BY THIS |
| | CODE SHALL BE PERMORMED IN A MANNER SO |
| | AS NOT TO ADVERSLY IMPACT THE CONDITION |
| | OF ADJACENT PROPERTY, UNLESS SUCH |
| | ACTIVITY IS PERMITTED TO AFFECT SAID |
| | PROPERTY PURSUANT TO A CONSENT BY THE |
| | APPLICABLE PROPERTY OWNER, UNDER TERMS & |
| | CONDITIONS AGREEABLE TO THE APPLICABLE |
| | PROPERTY OWNER.THIS INCLUDES BUT IS NOT |
| | LIMITED TO THE CONTROL OF DUST, NOISE, |
| | WATER OR DRAINAGE RUN-OFF, DEBRIS, AND |
| | THE STORAGE OF CONSTRUCTION MATERIALS. |
| | NEW CONSTRUCTION ACTIVITY SHALL NOT |
| | ADVERSELY IMPACT HISTORICSURFACE WATER |
| | DRAINAGE FLOWS SERVING ADJACENT |
| | PROPERTIES, & MAY REQUIRE SPECIAL |
| | DRAINAGE DESIGNCOMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED |
| | SITES.ACCORDINGLY, DEVELOPERS, |
| | CONTRACTORS, AND OWNERS OF ALL NEW |
| | RESIDENTIAL DEVELOPMENET, INCLUDING |
| | ADDITIONS, POOLS, PATIOS, DRIVEWAYS, |
| | DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN |
| | EXCESS OF 800SQ FT OF PERMEABLE LAND |
| | AREA ON ANY PARCELL SHALL AS A PERMIT |
| | CONDITION, PROVIDE A PROFESSIONALY |
| | PREPARED DRAINAGE PLAN CLEARLY |
| | INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE |
| | IMPROVEMENT, A CERTIFICATE FROM A |
| | LICENSED ENGINEER SHALL BE SUBMITTED TO |
| | THE INSPECTOR IN ORDER TO RECEIVE |
| | APPROVAL OF THE FINAL INSPECTION. |
| | |
| | 4) 109.3.10.1 HURICANE PROTECTION. |
| | IT SHALL BE UNLAWFUL FOR ANY PERSON TO |
| | ALLOW CONSTRUCTION RELATED MATERIALS |
| | EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR |
| | OTHERWISE UNSECURED AT A CONSTRUCTION |
| | SITE FROM 24 HRS. AFTER A HURRICANE |
| | WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN |
| | LIFTED. ALL SUCH CONSTRUCTION MATERIALS, |
| | EQUIPMENT AND DEBRIS SHALL BE EITHER |
| | REMOVED FROM THE CONSTRUCTION SITE OR |
| | SECURED IN SUCH A MANNER AS TO MINIMIZE |
| | THE DANGER OF SUCH CONSTRUCTION |
| | MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM |
| | HIGHWINDS. |
| | ANY PERSONS WHO FAILS TO COMPLY TO |
| | REMOVE OR SECURE THE CONSTRUCTION |
| | MATERIALS EQUIPMENT AND DEBRIS WITHIN |
| | 24 HRS AFTER A HURRICANE WATCH HAS BEEN |
| | ISSUED SHALL BE SUBJECT TO A FINE NOT TO |
| | EXCEED $500.00. |
| | IN ADDITION TO THE ABOVE, A LICENSED |
| | CONTRACTOR WHO VIOLATES THIS SECTION |
| | SHALL BE SUBJECT TO DISCIPLINE PURSUANT |
| | TO SECTION 113 OF THIS CHAPTER. |
| | |
| | 5) 110.2* W. P. B. ADMINISTRATIVE CODE, |
| | INFORMATION THAT IS REQUIRED FOR RECORD |
| | KEEPING & FOR CERTIFICATE OF OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PERMIT WAS ISSUED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT. |
| | |
| | |
| | G) NUMBER OF FLOORS |
| | |
| | |
| | H ) NUMBER OF ROOMS |
| | |
| | I) SQ. FT. LIV SPACE/ FL |
| | |
| | J) SQ. FT. FOOTPRINT |
| | |
| | K) SQ. FT. UNDER ROOF (TOTAL) |
| | |
| | L) OCCUPANT LOAD |
| | |
| | M) FLOOD ZONE |
| | |
| | N) FLOOD ELEVATION |
| | |
| | O)L.O.M.R. |
| | |
| | 6) WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 7) 1609.1.4 PROTECTION OF OPENINGS. |
| | IN WIND-BORNE DEBRIS REGIONS, EXTERIOR |
| | GLAZING THAT RECEIVES POSITIVE PRESSURE |
| | IN THE LOWER 60 FEET (18.3 M) IN |
| | BUILDINGS SHALL BE ASSUMED TO BE |
| | OPENINGS AND THE BALANCE OF GLAZED |
| | OPENINGS IN THE REST OF THE BUILDING |
| | SHALL BE ASSUMED TO BE ZERO UNLESS SUCH |
| | GLAZING THAT RECEIVES POSITIVE PRESSURE |
| | IS IMPACT RESISTANT OR PROTECTED WITH AN |
| | IMPACT RESISTANT COVERING MEETING THE |
| | REQUIREMENTS OF SSTD 12, ASTM E 1886 AND |
| | ASTM E 1996, OR MIAMI-DADE TAS 201, 202 |
| | AND 203 REFERENCED THEREIN AS FOLLOWS: |
| | 1.GLAZED OPENINGS LOCATED WITHIN 30 |
| | FEET (9.1 M) OF GRADE SHALL MEET THE |
| | REQUIREMENTS OF THE LARGE MISSILE TEST. |
| | 2.GLAZED OPENINGS LOCATED MORE THAN |
| | 30 FEET (9.1 M) ABOVE GRADE SHALL MEET |
| | THE PROVISIONS OF THE SMALL MISSILE |
| | TEST. |
| | |
| | 8) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 9) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) FIXED WINDOWS |
| | B) MULLIONS VERTICAL & HORIZONTAL |
| | C) GLAZED DOORS W/ TRANSOMS. |
| | D) STORM SHUTTERS |
| | E) TRUSS ANCHORS |
| | F) ROOF ASSEMBLIES |
| | |
| | 10) 1802.2.1 QUESTIONABLE SOIL. |
| | WHERE THE SAFE-SUSTAINING POWER OF THE |
| | SOIL IS IN DOUBT, OR WHERE ALOAD |
| | BEARING VALUE SUPERIOR TO THAT SPECIFIED |
| | IN THIS CODE IS CLAIMED, THE BUILDING |
| | OFFICIAL SHALL REQUIRE THAT THE |
| | NECESSARY INVESTIGATION BE MADE. SUCH |
| | INVESTIGATION SHALL COMPLY WITH THE |
| | PROVISIONS OF SECTIONS 1802.4 THROUGH |
| | 1802.6 . |
| | |
| | 11) PROVIDE A SITE PLAN WITH ALL |
| | STRUCTURES WITH DIMENSIONS BETWEEN |
| | BUILDINGS AND PROPERTY LINES.TABLE 601, |
| | TABLE 602. |
| | 503.1.3 BUILDINGS ON SAME LOT . |
| | TWO OR MORE BUILDINGS ON THE SAME LOT |
| | SHALL BE REGULATED AS SEPARATE BUILDINGS |
| | OR SHALL BE CONSIDERED AS PORTIONS OF |
| | ONE BUILDING IF THE HEIGHT OF EACH |
| | BUILDING AND THE AGGREGATE AREA OF |
| | BUILDINGS ARE WITHIN THE LIMITATIONS OF |
| | TABLE 503 AS MODIFIED BY SECTIONS 504 |
| | AND 506 . THE PROVISIONS OF THIS CODE |
| | APPLICABLE TO THE AGGREGATE BUILDING |
| | SHALL BE APPLICABLE TO EACH BUILDING. |
| | |
| | 12A) SHEET A-1 BUILDING NOMENCLATURE IS |
| | FROM THE 2001 FBC.RECLASSIFY TO THE 2004 |
| | FBC. |
| | |
| | 12B) SHEET S-5 STRUCTURAL NOTES |
| | INDICATES DESIGNED TO THE 2001 FBC WIND |
| | CHAPTER 1606. |
| | |
| | 13) SHOW ON SITE PLAN, |
| | 11-4.1.2 (1)AT LEAST ONE ACCESSIBLE |
| | ROUTE COMPLYING WITH SECTION 11-4.3 |
| | SHALL BE PROVIDED WITHIN THE BOUNDARY OF |
| | THE SITE FROM PUBLIC TRANSPORTATION |
| | STOPS, ACCESSIBLE PARKING SPACES, |
| | PASSENGER LOADING ZONES IF PROVIDED, AND |
| | PUBLIC STREETS OR SIDEWALKS, TO AN |
| | ACCESSIBLE BUILDING ENTRANCE. |
| | (2)AT LEAST ONE ACCESSIBLE ROUTE |
| | COMPLYING WITH SECTION 11-4.3 SHALL |
| | CONNECT ACCESSIBLE BUILDINGS, ACCESSIBLE |
| | FACILITIES, ACCESSIBLE ELEMENTS, AND |
| | ACCESSIBLE SPACES THAT ARE ON THE SAME |
| | SITE. |
| | |
| | 14) THE PLAN REVIEW DOESN'T INDICATE IF |
| | THIS TO BE A SHELL OR INCLUDE TENANT |
| | BUILD OUT. THE EXITS WORK AS SHOWN BUT |
| | MAY HAVE PROBLEMS WITH BUILD OUT. |
| | |
| | 15) DISCREPANCY IN PLANS, A2 DETAIL OF |
| | TOWER CUT SECTION DETAIL2 ON A4.1 WHEN |
| | TURNING TO DETAIL INDICATES A 2X6 GAL |
| | 16G METAL STUD. THE SAME DETAIL |
| | REFRENCES A BOTTOM TRACK ASSEMBLY DETAIL |
| | 5 ON A-2 WHICH IS A TILT WALL PARAPET |
| | DETAIL? PLEASE CORRECT. |
| | |
| | 16)ROOF ASSEMBLIES PRODUCT APPROVAL |
| | INFORMATION REQUIRED: |
| | (FLAT ROOF) |
| | ) THIS ROOF IS MISSING OR NOT IN |
| | COMPLIANCE WITH THE FOLLOW ITEMS: |
| | |
| | ___ CONTRACTOR DID NOT PROVIDE THE MEAN |
| | |
| | ROOF HEIGHT. |
| | |
| | ___ CONTRACTOR DID NOT INDICATE THE ROOF |
| | PITCH. |
| | |
| | ___ CONTRACTOR FAILED TO INDICATE WHICH |
| | SYSTEM TO BE USED. |
| | |
| | ___ THE SYSTEM PROVIDED HAS A LOW |
| | PRESSURE FOR ZONE ___ . |
| | |
| | ___ THE SYSTEM PROVIDED STATES |
| | LIMITATION# 7, SHOULD THE FASTENER |
| | RESISTANCE BE LESS THAN THAT |
| | REQUIRED, AS DETERMINED BY THE |
| | BUILDING OFFICIAL, A REVISED |
| | FASTENER SPACING, PREPARED , SIGNED |
| | AND SEALED BY A FLORIDA REGISTERED |
| | PROFESSIONAL ENGINEER, REGISTERED |
| | ARCHITECT OR REGISTERED ROOF |
| | CONSULTANT MAY BE SUBMITTED. |
| | |
| | ___THE SYSTEM PROVIDED INDICATES |
| | LIMITATION# 9, NO ENHANCED |
| | FASTENING ALLOWED. |
| | |
| | 17)ENERGY13-101.1.6 SHELL BUILDINGS. |
| | NONRESIDENTIAL BUILDINGS THAT ARE |
| | PERMITTED PRIOR TO DESIGN COMPLETION OR |
| | WHICH WILL BE FINISHED IN SECTIONS AT A |
| | TIME AFTER CONSTRUCTION OF THE SHELL |
| | SHALL COMPLY WITH EITHER METHOD B OR C |
| | OF SUBCHAPTER 13-4 OF THE CODE PRIOR TO |
| | GRANTING OF A PERMIT TO BUILD. ALL |
| | ASSUMPTIONS MADE ABOUT FEATURES NOT |
| | INSTALLED UNTIL LATER THAT ARE NOT ON |
| | THE BUILDING PLANS SHALL BE LISTED AND |
| | APPENDED TO THE COMPLIANCE FORM |
| | SUBMITTED TO THE BUILDING DEPARTMENT. |
| | UNLESS THE BUILDING IS COMPLETED AS PER |
| | ALL ASSUMPTIONS MADE IN THE ORIGINAL |
| | CODE COMPLIANCE SUBMITTAL, A REVISED |
| | CODE SUBMITTAL(S) USING METHODS A, B OR |
| | C SHALL BE SUBMITTED WHEN COMPLETION OF |
| | THE BUILDING (OR PART OF THE BUILDING) |
| | IS PERMITTED. |
| | |
| | 18) BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |