| 2006-03-16 00:00:00 | ******DENIED****** | | | | | | 1) AN ADDRESS IS REQUIRED ON BUILDING | | | AND SHALL BE A MINIMUM OF 6" IN HEIGHT | | | AND CONTRASTING TO THE BACKGROUND. | | | | | | 2) ARE FIRE SPRINKLER AND FIRE ALARM | | | SYSTEMS PLANNED FOR THE BUILDING? SHT | | | A-1 INDICATES UNSPRINKLED. | | | | | | 3) 2A-10B,C RATED FIRE EXTINGUISHERS ARE | | | REQUIRED AND SHALL BE MOUNTED AT | | | DISTANCES NOT TO EXCEED 75'. | | | | | | 4) PLEASE INDICATE THE LOCATION AND | | | BUILDING DISTANCE TO THE CLOSEST FIRE | | | HYDRANT. | | | | | | 5) PLEASE PROVIDE FLAME RETARDANT | | | INFORMATION FOR THE PROPOSED AWNING. | | | | | | 6) WILL BUILDING HAVE ABILITY TO MEET | | | TENANT SEPARATION REQUIREMENTS FOR | | | FUTURE BUILDOUTS? | | | | | | 7) PLANS DON'T ILLUSTRATE THE LOCATIONS | | | OF EXIT SIGNS AND EMERGENCY LIGHTING | | | FACILITIES. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLANS REVIEW (561) 805-6722 |
|