| 2006-02-01 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR A GAS PERMIT: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENTHS PER FBC-2004 |
| | FUEL GAS CODE. (NOTE: YOUR DRAWING SHOWS |
| | ONLY 35' OF U/G PE PIPE. HOW LONG ARE |
| | THE RISERS?) |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | (NOTE: YOUR DRAWING ONLY SHOWS 3/4" PE |
| | PIPE. WHAT SIZE, AND MATERIAL ARE THE |
| | RISERS?) |
| | 3. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). (NOTE: HOUSE HAS EXISTING GAS, |
| | EXISTING HOUSE AND TOTAL BTU LOADS NEED |
| | TO BE NOTED ON DRAWING.) |
| | |
| | 4. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). (NOTE: THE |
| | LONGEST LENGTH ON SYSTEM NEEDS TO NOTED |
| | ON DRAWING IN ORDER TO CHECK SIZING WITH |
| | TABLES.) |
| | |
| | END OF COMMENTS: |
| | |