| 2006-02-14 00:00:00 | *** DENIED *** | | | 1) A/C SYSTEM #3 IS NOT ON ENERGY | | | CALCULATIONS, PLEASE CORRECT. | | | | | | 2) ENERGY CALCULATIONS NEED TO BE SIGNED | | | BY OWNER/AGENT. | | | | | | 3) JOB ADDRESS NEEDS TO BE ON ALL MECH. | | | PLAN SHEETS. | | | | | | 4) MECH. PLANS NEED NAME AND SIGNATURE | | | OF DESIGNER. ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA | | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN. PER | | | FBC 104.2.1 . | | | | | | 5) NEED TO SHOW CLOTHES DRYER VENT | | | LOCATION AND TERMINATION ON MECH. PLANS. | | | | | | 6) DUCTS (FLEX) NOT SIZED IN MASTER | | | BEDROOM. | | | | | | 7) DOOR TO AHU #2 IS NOT ON BUILDING | | | FLOOR PLAN PLEASE CORRECT. | | | | | | 8) CLOSET FOR AHU #3 NOT SHOWING ON | | | BUILDING FLOOR PLAN PLEASE CORRECT. | | | | | | 9) 3RD FLOOR BBQ GRILL UNDER COVERED | | | DECK NEEDS AN APPROVED HOOD, PER 2004 | | | FBC/M 505.3 . | | | | | | 10) PLEASE NOTE THAT DUCT WORK IN A | | | GARAGE NEEDS TO BE METAL WITH NO | | | OPENINGS IN GARAGE, PER 2004 FBC/R | | | 309.1.1 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|