| Plan Review Notes For Permit 06010964 |
| Permit Number |
06010964 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-02-03 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE SMALL APPLIANCE CALCULATION IS | | | INCORRECT, SEE 220.16, 1500 VA PER | | | CIRCUIT. | | | | | | 2} PLEASE LOCATE THE AIR HANDLERS AND | | | CONDENSING UNITS ON PLAN. SHOW | | | DISCONNECTING MEANS PER 110.26 AND | | | 440.14, AND RECEPTACLE LOCATIONS PER | | | 210.63, LIGHTING PER 210.70(A)(3). | | | | | | 3} THE LOAD CALCULATION FOR THE A/C | | | SYSTEMS DOES NOT CORRESPOND WITH THE | | | MECHANICAL SPECIFICATION. PLEASE | | | CORRELATE AND RECALCULATE PER 220.30 OR | | | 220.31. | | | | | | 4} PLEASE SEE 210.8(A)(7) FOR GFI | | | REQUIREMENTS AT THE WET BAR. | | | | | | 5} IF THE TUB UNIT IN THE MASTER BATH IS | | | THE SPA REFERENCED IN THE LOAD CALCS, | | | SHOW COMPLIANCE WITH 680.43. SWITCHES | | | SHALL BE LOCATED AT LEAST 1.5 M (5 FT), | | | MEASURED HORIZONTALLY, FROM THE INSIDE | | | WALLS OF THE SPA OR HOT TUB IS PART OF | | | THAT ARTICLE. | | | | | | 6} A SMOKE DETECTOR IS REQUIRED ON THE | | | THIRD LEVEL PER R313.1 FBC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|