Plan Review Notes
Plan Review Notes For Permit 06010964
Permit Number 06010964
Review Stop E
Sequence Number 1
Notes
Date Text
2006-02-03 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE SMALL APPLIANCE CALCULATION IS
 INCORRECT, SEE 220.16, 1500 VA PER
 CIRCUIT.
  
 2} PLEASE LOCATE THE AIR HANDLERS AND
 CONDENSING UNITS ON PLAN. SHOW
 DISCONNECTING MEANS PER 110.26 AND
 440.14, AND RECEPTACLE LOCATIONS PER
 210.63, LIGHTING PER 210.70(A)(3).
  
 3} THE LOAD CALCULATION FOR THE A/C
 SYSTEMS DOES NOT CORRESPOND WITH THE
 MECHANICAL SPECIFICATION. PLEASE
 CORRELATE AND RECALCULATE PER 220.30 OR
 220.31.
  
 4} PLEASE SEE 210.8(A)(7) FOR GFI
 REQUIREMENTS AT THE WET BAR.
  
 5} IF THE TUB UNIT IN THE MASTER BATH IS
 THE SPA REFERENCED IN THE LOAD CALCS,
 SHOW COMPLIANCE WITH 680.43. SWITCHES
 SHALL BE LOCATED AT LEAST 1.5 M (5 FT),
 MEASURED HORIZONTALLY, FROM THE INSIDE
 WALLS OF THE SPA OR HOT TUB IS PART OF
 THAT ARTICLE.
  
 6} A SMOKE DETECTOR IS REQUIRED ON THE
 THIRD LEVEL PER R313.1 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  