| Notes |
| Date |
Text |
| 2006-02-14 00:00:00 | ******PROVISO****** | | | | | | 1) PLANS HAVE BEEN RED LINED IN | | | REFERENCE TO SUPPLY PIPE SERVING (2) | | | HYDRANTS. | | | | | | 2) MONITORING SHALL BE UL CERTIFIED FOR | | | CENTRAL STATION SERVICE. | | | | | | 3) ELECTRONIC SUPERVISION REQUIRED ON | | | ALL CONTROL VALVES INCLUDING OS&Y VALVES | | | AT THE WATER TANK. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLANS REVIEW (561) 805-6722 |
|