Plan Review Notes
Plan Review Notes For Permit 06010960
Permit Number 06010960
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-02-14 00:00:00******PROVISO******
  
 1) PLANS HAVE BEEN RED LINED IN
 REFERENCE TO SUPPLY PIPE SERVING (2)
 HYDRANTS.
  
 2) MONITORING SHALL BE UL CERTIFIED FOR
 CENTRAL STATION SERVICE.
  
 3) ELECTRONIC SUPERVISION REQUIRED ON
 ALL CONTROL VALVES INCLUDING OS&Y VALVES
 AT THE WATER TANK.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722