| 2006-05-02 00:00:00 | ********* UNSAT 2ND REVIEW ********* |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW AND SOME NEW NOTES DUE TO PLANS |
| | AND INFORMATION NOW SHOWN. |
| | |
| | |
| | 1) NOTE: PLEASE SEE 700.12E FOR |
| | CIRCUITING OF EM/ EXT LTS. PLEASE SEE |
| | PLANS SEEM TO BE CIRCUITED CORRECTLY, |
| | HOWEVER PLEASE SEE PANEL SCHEDULE WHICH |
| | INDICATE THESE ONLY CIRCUITED TO ONE |
| | CIRCUIT. |
| | PLEASE CORRELATE CIRCUITING WITH PLANS |
| | AND PANEL SCHEDULE, |
| | |
| | 2) NOTE: PLEASE INDICATE A NEW OR |
| | EXISTING SIGN CIRCUIT AS REQUIRED PER |
| | 600.5. |
| | A RESPONSE NOTE ON PLANS INDICATES |
| | "FASCIA SIGNS DO NOT REQUIRE ELECTRIC." |
| | HOWEVER PLEASE SEE CODE AS REFERENCE AS |
| | IS DOES NOT MATTER WHETHER OR NOT AN |
| | ELECTRICAL SIGN IS INSTALLED, THE MEANS |
| | OF AN ELECTRICAL CIRCUIT IS REQUIRED FOR |
| | USE AT THIS TIME OR FUTURE USE. |
| | |
| | 3) NOTE: PLEASE SEE PLANS ARE NOW COMING |
| | IN WITH OUT ANY SIGNATURE, SEAL, TITLE |
| | BLOCK OR THE PRINTED NAME AND SIGNATURE |
| | OF A DESIGN PROFESSIONAL. |
| | PLEASE SEE ORIGINAL PLANS AND ALL OTHER |
| | SHEETS CONTAINED THIS AND NOW PLANS ARE |
| | REVISED TO INDICATE AN "ELECTRICAL |
| | CONTRACTOR". |
| | PLEASE KNOW, DUE TO THE SCOPE OF WORK , |
| | PLANS SHALL BE SIGNED AND SEALED BY A |
| | MIN OF AN ARCHITECT OR PE. |
| | |
| | 4) NOTE: PLEASE SPECIFY ANY |
| | CLASS/DIVISION LOCATIONS ON PLANS WHERE |
| | APPLICABLE AT OYGEN STORAGE. |
| | WILL ANY TREATMENTS BE ADMINISTERED AT |
| | THIS LOCATION? IF NOT, PLEASE NOTE ON |
| | PLANS. |
| | PLEASE SEE OCCUPANCY WAS DECCLARED ON |
| | PLANS AND THESE PLANS INDICATE |
| | "BUSINESS", HOWEVER THERE IS SOME |
| | CONFUSION OVER "PATIENT SETUP ROOM" AND |
| | "RESPITORY OFFICE" IS THIS A SALES |
| | OFFICE OR A TREATMENT ROOM? |
| | |
| | 5)NOTE: PLEASE SEE EXISTING PANELS ARE |
| | NOW BEING SHOWN, HOWEVER LOCATION OF |
| | THESE COULD NOT BE LOCATED ON PLANS. |
| | PLEASE SHOW AND VERIFY PER 240.24,110.26 |
| | |
| | 6) NOTE: PLEASE VERIFY SIZES OF |
| | CONDUCTORS TO THE AHU'S AS THEY ARE |
| | SHOWN AS 10KW, 60A OCP ON #8? |
| | IT IS NOTED THAT THESE ARE EXISTING, |
| | HOWEVER PLEASE VERIFY. |
| | 240.4,310.16 |
| | |
| | 7) NOTE: PLEASE SEE FBC CHAPTER 13 , |
| | 13-415.1.ABC.1.1 AND .2. |
| | 13-415.1.ABC.3 |
| | |
| | **PLEASE SEE FS 553.80(2)(B) WITH |
| | RESPECT TO REPEAT COMMENTS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | BEFORE RESUBMITTING PLANS. |
| | PLEASE BE SURE TO ATTACHED ONE COPY OF |
| | ANY OF THE OLD/VOIDED SHEETS . |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |