| 2006-02-27 00:00:00 | *********UNSAT ********** |
| | |
| | 1)NOTE: PLEASE SEE THE PLANS REFERENCE |
| | THE 2005 NEC , WHEN WE ARE CURRENTLY |
| | UNDER THE 2002 NFPA-70. |
| | PLEASE ALSO KNOW, WE ARE UNDER THE 2003 |
| | NFPA-101, AND 2002 NFPA-72 |
| | |
| | 2)NOTE: PLEASE SEE FIXTURE LEGEND DOES |
| | NOT INDICATE ANY BATTERY BACK UP FOR EM |
| | LTS. |
| | PLEASE SEE LS 101 7.8, 7.9 WHICH |
| | REQUIRES A MIN. PLEASE ALSO SEE FIRE |
| | REVIEW COMMENTS. |
| | |
| | 3)NOTE: PLEASE SEE ADDRESS ON PLANS |
| | MENTIONS "OLD " OKEECHOBEE RD. PLEASE |
| | SEE AND KNOW, THERE IS ONLY A |
| | "OKEECHEOBEE RD" IN CITY OF WEST PALM |
| | BEACH. |
| | PLEASE ADJUST PLANS AND PERMIT |
| | APPLICATION. |
| | |
| | 4)NOTE: PLEASE CORRELATE CIRCUITING ON |
| | PLANS WITH PANEL SCHEDULE(S). PLEASE SEE |
| | EM/EXT LTS, SW RECEPTS? |
| | 215.5 |
| | |
| | 5)NOTE: PLEASE CLARIFY IF THERE IS A NEW |
| | OR EXISTING SIGN CIRCUIT(S). 600.5 |
| | |
| | 6)NOTE: PLEASESEE ITEMS ON PANEL |
| | SCHEDULE WHICH SHOWS AWG AND OCP, |
| | HOWEVER DOES NOT INDICATE WHAT THESE |
| | ARE. |
| | 215.5 |
| | |
| | 7)NOTE: PLEASE SUBMIT LOADS AND CALCS |
| | FOR USE. 220.3,220.10,220.11,220.13 ETC |
| | 215.3, 230.42 FOR CONTINUOUS LAODS. |
| | |
| | 8)NOTE: |
| | |
| | 9)NOTE: PLEASE SEE NUMEROUS ELECTRICAL |
| | NOTES ON PLANS WHICH REFLECT ELECTRICAL |
| | WORK FOR WHAT APPEARS TO BE A |
| | RESIDENTIAL USE? RECEPT SPACING,,ETC . |
| | PLEASE SEE NOTES SHOULD REFLECT COMM |
| | SCOPE OF WORK. |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | AND ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE COPY OF OLD SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |