| Date |
Text |
| 2006-03-22 00:00:00 | 1) 110.2* W. P. B. ADMINISTRATIVE CODE, |
| | INFORMATION THAT IS REQUIRED FOR RECORD |
| | KEEPING & FOR CERTIFICATE OF OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PERMIT WAS ISSUED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT. |
| | |
| | 2) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 3) NOTE:105.9 ASBESTOS. THE ENFORCING |
| | AGENCY SHALL REQUIRE EACH BUILDING |
| | PERMIT FOR THE DEMOLITION OR RENOVATION |
| | OF AN EXISTING STRUCTURE TO CONTAIN AN |
| | ASBESTOS NOTIFICATION STATEMENT WHICH |
| | INDICATES THE OWNER?S OR OPERATOR?S |
| | RESPONSIBILITY TO COMPLY WITH THE |
| | PROVISIONS OF SECTION 469.003, FLORIDA |
| | STATUTES, AND TO NOTIFY THE DEPARTMENT |
| | OF ENVIRONMENTAL PROTECTION OF HIS OR |
| | HER INTENTIONS TO REMOVE ASBESTOS, WHEN |
| | APPLICABLE, IN ACCORDANCE WITH STATE AND |
| | FEDERAL LAW. |
| | |
| | 4)(2004 FBC) 106.1.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. CONSTRUCTION |
| | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE & |
| | EXTENT OF THE WORK PROPOSED & SHOW IN |
| | DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND REVELENT |
| | LAWS, ORDINANCES, AND RULES AND |
| | REGULATIONS AS DETERMINED BY THE |
| | BUILDING OFFICIAL. |
| | |
| | 5) INDICATE CLEARLY ON THE DRAWINGS WHAT |
| | TYPE OF BUSINESS WILL BE AT THIS |
| | LOCATION AND THE SQUARE-FOOTAGE OF |
| | WAREHOUSE AND THE PATIENT/OFFICE AREA. |
| | |
| | 6) WHAT TYPE OF MATERIALS WILL BE STORED |
| | IN THE WAREHOUSE AND WHAT AMOUNT WILL BE |
| | STORED. WILL THE BE FORK-LIFTS BE |
| | DRIVING AROUND IN THE WAREHOUSE? |
| | |
| | 7) A MORE DETAIL DRAWING FOR THE HOLDING |
| | AREA FOR THE OXYGEN TANK IS REQUIRED |
| | SHOWING HOW THE TANKS WILL BE PREVENTED |
| | FROM TIPPING OVER. ALSO THE SIZE AND |
| | TYPE OF TANKS SHALL BE INDICATED ON THE |
| | PLANS. |
| | |
| | 8) WHAT IS THE REASON FOR HAVING A |
| | PATIENT SERVICE TECH OUT IN THE |
| | WAREHOUSE AREA. |
| | |
| | 9) THE PLANS INDICATE THE OCCUPANCY AS : |
| | SMALL ASSEMBLY HOWEVER, LOOKING AT THE |
| | DRAWINGS AND READING THE DEFINITION OF |
| | ASSEMBLY, THESE PLANS DO NOT FALL UNDER |
| | THAT TYPE OF OCCUPANCY. SEE FBC SECTION |
| | "303 AND 304" FOR THE CORRECT TYPE OF |
| | OCCUPANCY. |
| | |
| | 10) SEE FBC.SEC 311 FOR THE TYPE OF |
| | STORAGE WHICH IS REQUIRED FOR THE |
| | BUILDING. STATE CLEARLY THE OCCUPANT |
| | LOAD OF THE BUILDING. |
| | |
| | 11) SHEET 2.1 MENTION "STUDIO" WHERE IS |
| | THE STUDIO ON THE PLANS? |
| | |
| | 12) THOSE PRODUCT APPROVALS WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL.WPB |
| | AMMENDMENT TO FBC 106.3.3 |
| | PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| | APPLICATION AFTER OCTOBER 1, 2003 ARE |
| | REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG. THE |
| | NEW ROLL UP DOOR NEEDS PRODUCT APPROVAL. |
| | |
| | 13) 11-4.1.6(2) DUTY TO PROVIDE AN |
| | ACCESSIBLE PATH OF TRAVEL TO ALTERED |
| | AREAS SHALL BE DEEMED DISPROPORTIONATE |
| | TO THE OVERALL ALTERATION WHEN THE COST |
| | EXCEEDS 20 % OF THE COST OF THE ALTERA- |
| | TION TO THE PRIMARY FUNCTION AREA. |
| | (A)(I) AN ACCESSIBLE ENTRANCE |
| | (II) AN ACCESSIBLE ROUTE |
| | (III) AT LEAST ONE ACCESSIBLE REST- |
| | ROOM FOR EACH SEX OR A SINGLE |
| | UNISEX RESTROOM |
| | (IIII) ACCESSIBLE TELEPHONE |
| | (IV) ELEMENTS SUCH AS PARKING, STOR- |
| | AGE OR ALARMS. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | TEL:(561)805-6726 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |