Plan Review Notes
Plan Review Notes For Permit 06010937
Permit Number 06010937
Review Stop B
Sequence Number 2
Notes
Date Text
2006-02-28 00:00:00 
  
 DENIED
  
 1) SYSTEM CHOSEN IN NOA DOES NOT MEET
 THE PRESSURES FOR WEST PALM BEACH OF
 -59.2 FOR PERIMITER AND -89.0 FOR
 CORNERS. THIS SYSTEM CARRIES A
 LIMITATION #9 WHICH DOES NOT ALLOW FOR
 INCREASED FASTENERS BY RATIONAL ANALYSIS
  
 2) ONLY LIMITATION #7 ALLOWS FOR
 ENHANCED FASTENERS AND THE CALCULATIONS
 MUST BE PERFORMED BY AN ENGINEER TO MEET
 THE REQUIREMENTS OF THIS PARTICULAR NOA
  
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716