Plan Review Notes
Plan Review Notes For Permit 06010914
Permit Number 06010914
Review Stop G
Sequence Number 1
Notes
Date Text
2006-01-31 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR A GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.(NOTE: YOUR DRAWING SHOWS
 ONLY 16' OF 1" POLY BEING USED U/G WHAT
 ARE THE LENGTHS OF THE RISERS)
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 (NOTE: YOUR DRAWING SHOWS ONLY 1" POLY
 BEING USED. IS THIS YOUR INTENT?)
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).(NOTE: HOUSE HAS EXISTING GAS,
 THE TOTAL BTU LOAD ON SYSTEM NEEDS TO BE
 NOTED ON DRAWING)
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).(NOTE: THE
 LONGEST LENGTH ON SYSTEM NEEDS TO BE
 NOTED ON DRAWING IN ORDER TO CHECK
 SIZING WITH TABLES)
  
 END OF COMMENTS
  
 REVIEW BY MIKE PERSON
 (561)805-6730
 FAX (561)805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVSNS
 (561)805-6721
  
  
  