Plan Review Notes
Plan Review Notes For Permit 06010911
Permit Number 06010911
Review Stop G
Sequence Number 1
Notes
Date Text
2006-01-31 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.(NOTE: YOUR DRAWING SHOWS
 ONLY 25' OF 1" U/G POLY. IS THIS YOUR
 INTENT?)
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 (NOTE: 1" POLY IS THE ONLY MATERIAL
 INDICATED ON DRAWING. IS THIS YOUR
 INTENT?)
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561)805-6730
 FAX(561)805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561)805-6721
  