| Notes |
| Date |
Text |
| 2006-02-09 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE DEMAND ON THE EM PANEL EXCEEDS | | | THE GENERATOR OUTPUT AND IS NONCOMPLIANT | | | WITH 702.5. | | | | | | 2} IT IS UNCLEAR ON THE SITE PLAN IF THE | | | ATS, GENERATOR, AND SUBPANEL ARE LOCATED | | | ON OR IN A SEPARATE STRUCTURE FROM THE | | | MAIN SERVICE. PLEASE CLARIFY AND SEE | | | ARTICLE 225.31 THROUGH 225.39. NOTE | | | 225.34 "GROUPING". THE ATS MUST COMPLY | | | WITH THIS ARTICLE IF USED AS A | | | DISCONNECT. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | | | | |
|