Plan Review Notes
Plan Review Notes For Permit 06010883
Permit Number 06010883
Review Stop B
Sequence Number 1
Notes
Date Text
2006-02-04 00:00:00ALL REPAIRS MUST COMPLY WITH THE
 EXISTING BUILDING REPAIR SECTION AND
 OTHER APPLICABLE SECTIONS.
 1)FBC 401.2 PERMITTED MATERIALS:EXCEPT
 AS OTHERWISE REQUIRED HEREIN,WORK SHALL
 BE DONE USING MATERIALS PERMITTED BY THE
 APPLICABLE CODE FOR NEW CONSTRUCTION OR
 USING LIKE MATERIALS SUCH THAT NO HAZARD
 TO LIFE,HEALTH OR PROPERTY IS CREATED.
  
 2)FBC 401.3 CONFORMANCE:THE WORK SHALL
 NOT MAKE THE BUILDING LESS CONFORMING TO
 THE
 BUILDING,PLUMBING,MECHANICAL,ELECTRICAL
 OR FIRE CODES OF THE JURISDICTION,OR TO
 ALTERNATIVE MATERIALS,DESIGN AND METHODS
 OF CONSTRUCTION,OR ANY PREVIOUSLY
 APPROVED PLANS,MODIFICATIONS,OR
 COMPLIANCE ALTERNATIVES,THAN IT WAS
 BEFORE THE REPAIR WAS MADE.
  
 3)FBC 1703.4.1 RESEARCH AND
 INVESTIGATION:
  
 A)REQUIRED SUBMITTAL: 2 COPIES OF THE
 TENDON PROFILE AND PLACEMENT PLAN
 APPLICABLE TO THE PROPOSED FLOOR
 REPAIR.INDICATE REPAIR LOCATION.
  
 B)EVIDENCE THAT THE PRELIMINARY FLOOR
 SLAB X-RAYS WERE COMPLETED.
  
 C)SUBMIT RESUME OF PREVIOUS POST-TENSION
 REPAIR WORK.
  
 D)ENGINEERING REPAIR LETTER SHOULD
 INDICATE THAT NO TYPE OF SHORING IS
 REQUIRED DURING THE REPAIR.